Mounting Threaded Bolts to the Interface Plate
Figure 10: Mounting the upper insulations to the threaded
bolts
1568911, Edition 2019-04, Version 0

6.1.4 Mounting the upper insulations to the threaded bolts

(See "Figure 10")
The 6 (Single version) or 12 (Duo version) hexagonal nuts M16② must
be mounted to the threaded bolts M16① at an exact distance to each oth-
er.
1.
For each threaded bolt M16① screw a hexagonal nut M16② onto
the threaded bolts M16①.
2.
Adjust the distance between the hexagonal nuts M16② and the in-
terface plate
to 150mm.
1
3.
Using a digital spirit level, align the hexagonal nuts M16② in a hori-
zontal position.
4.
Place 1 flat washer with an external diameter of 34mm③ .
5.
Place 1 plastic insulating disc④ (as illustrated in the Figure) in such
a way that the flat washer with an external diameter of 34mm③
(see arrow in the detailed representation in the Figure) sits in the
plastic insulating disc④.
6.
Using an adhesive or elastic tape, attach the plastic insulating
disc④ to the threaded bolts M16①.
7.
Continue the installation as described in Chapter 7 on Page 32 or
Chapter 8 on Page 36.