M800W/M80W Series Connection and Setup Manual
26 Setting the Tool Entry Prohibited Range
The stored stroke limits I, II, IIB, IB and IC are handled as follows.
Prohibited
Type
range
- Set by the machine tool builder.
- When used with II, the confined range
I
Outside
designated by the two functions becomes the
movement valid range.
II
Outside
- Set by the user.
- Select II or IIB with the
parameters.
IIB
Inside
IB
Inside
- Set by the machine tool builder.
IC
Outside - Set by the machine tool builder.
-
The stroke check will not be executed when both maximum and minimum value are set to the same value.
-
This function is valid after the reference position return if the system does not apply the absolute position detection
system.
-
Before the machine enters the prohibited range, an error "M01 Operation error 0007" (S/W stroke end) will occur,
and the machine movement will stop. The alarm can be reset by moving the erroneous axis in the opposite
direction.
-
During automatic operation, if an alarm occurs with even one axis, all axes will decelerate to a stop.
-
During manual operation, only the axis that caused the alarm will decelerate to a stop.
-
The axis will always stop at a position before the prohibited range.
-
The distance between the prohibited range and stop position will depend on the feedrate, etc.
Description
- "#8210 OT-
INSIDE" = "0"
- Used with I.
- "#8210 OT-
INSIDE" = "1"
509
Range setting parameters
"#2013 OT -
- Reference position return is
(Soft limit I -)"
completed.
"#2014 OT +
- #2013 and #2014 are not set
(Soft limit I +)"
to the same value.
- Reference position return is
completed.
"#8204 OT-CHECK-N"
- #8204 and #8205 are not set
"#8205 OT-CHECK-P"
to the same value.
- "#8202 OT-CHECK OFF" =
"0"
"#2061 OT_1B-
- Reference position return is
(Soft limit IB-)"
completed.
"#2062 OT_1B+
- #2061 and #2062 are not set
(Soft limit IB +)"
to the same value.
- Reference position return is
"#2061 OT_1B-
completed.
(Soft limit IB-)"
- #2061 and #2062 are not set
"#2062 OT_1B+
to the same value.
(Soft limit IB +)"
- "#2063 OT_1Btype (Soft limit
IB type)" = "2"
Validating conditions
IB-1501268-K