Intensity Of Flame During Curve Settings - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

27.11.13 Intensity of flame during curve settings

/reset
Building Technologies
When setting the curve and the curvepoint is displayed, you can press
intensity of flame. When pressing the button for >1 s, a change to parameter 954 is
made; when releasing the button, you return to the curvepoint.
P
V
h min s
P
V
h min s
Basic documentation LMV37.4...
27 Parameter level
Example: Curvepoint Low-flame position P1.
%
Change to parameter 954
/reset
>1 s
Parameter 954: flashes.
The intensity of flame in % is shown on the right.
Example: 954: 0.0
Release
to return to curvepoint Low-fire
/reset
position P1.
%
to show the
/reset
221/267
CC1P7546en
17.12.2018