Siemens LMV37.4 Series Basic Documentation page 95

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Building Technologies
Multistage operation X5-03 (stage 2, pin 3 / stage 3, pin 2)
In multistage operation, 1 or 2 thermostats can be connected to activate the different
burner stages. Multistage operation is possible only when firing on oil.
If neither input «Stage 2» nor input «Stage 3» is active, the burner switches to
«Stage 1».
If input «Stage 2» becomes active, the burner switches to the second stage.
If input «Stage 3» becomes active, the burner switches to the third stage. In that case,
input «Stage 2» can be active or inactive. The third stage can only be activated with 3-
stage operation.
Load controller (LR) (OPEN)
Load controller (LR) (CLOSED)
Load controller (LR) (ON/OFF)
Figure 70: 2-stage operation X5-03
Load controller (LR) (OPEN)
Load controller (LR) (CLOSED)
Load controller (LR) (ON/OFF)
Figure 71: 3-stage operation X5-03
Basic documentation LMV37.4...
9 Connection to load controllers
LMV...
L
Bild 317e/0913
LMV...
L
Bild 318e/0913
ON/OFF
ON/OFF
95/267
CC1P7546en
17.12.2018