Possible Start Preventions; Repetition Counter - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

60/267
Building Technologies
7.5.4.3.

Possible start preventions

On the normal display, error code 201 is translated to text display OFF UPr (UPr =
unprogrammiert = not programmed); the numerical value appears in the error history.
Error
Diagnostic
code
code
201
1
OFF UPr
2...3
4...7
8...15
16...31
3
4
4
2
14
64
21
64
22
1
OFF S
83
#
97
#
0
No.
Parameter
Standardized speed
Index 0 = speed 1
Index 1 = speed 2 (internal monitoring)
642
Fuel 1:
Index 2 = fuel 1: Speed 1
Index 3 = fuel 1: Speed 2 (internal monitoring)
935
Absolute speed
936
Standardized speed
7.5.4.4.

Repetition counter

Repetition counters are available for different types of errors. They are used to set the
number of errors permitted until lockout occurs. The last error initiates lockout. When
setting the number of errors to 3, for example, a repetition (restart) takes place after the
first 3 errors, and after the third error, the LMV37.4 initiates lockout.
Note
Setting 16 means an infinite number of repetitions = no lockout.
Basic documentation LMV37.4...
7 Basic unit LMV37.4
Meaning for the LMV37.4
No operating mode selected
No fuel train defined
No curve defined
Standardized speed undefined
Backup / restore was not possible
Other start preventions:
Air pressure on – start prevention
Extraneous light during startup – start prevention
POC open – prevention of startup
POC open – prevention of startup (software version
V02.00)
Safety loop / burner flange open – prevention of startup
Speed error VSD
Error relay supervision
Safety relay contacts have welded or external power supply
fed to safety relay
CC1P7546en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents