26
Service level
Note
When on the service level, you can press
parameter.
Instead of pressing
Note
Press
P
Parameter
26.1 Display of service level
P
/reset
Building Technologies
The service level is used to display information about errors including the error history
and information about the LMV37.4.
, you can also press
ESC
or
for >3 s to return to the normal display.
/reset
V
h min s
%
Parameter value
Figure 102: Service level
V
h min s
%
No.
Parameter
Service level
954
Intensity of flame
960
Actual flow rate (fuel throughput in m³/h, l/h, ft³/h, gal/h)
121
Manual output
Undefined = automatic operation
922
Incremental position of actuators
Index 0 = fuel
Index 1 = air
936
Standardized speed
161
Number of faults
701
Error history: 701-725.01.Code
●
Error history: 701-725.02.Diagnostic code
●
Error history: 701-725.03.Error class
●
Error history: 701-725.04.Phase
●
Error history: 701-725.05.Startup counter
●
Error history: 701-725.06.Output
725
Error history: Oldest error in the history
Basic documentation LMV37.4...
26 Service level
or
to display the next or the previous
for <1 s.
/reset
Note!
No change of values on the service level.
If characters ._._ are displayed by the parameter, the
value may consist of more than 5 digits.
Press
for >1 s and <3 s to display the value.
/reset
Press
for >3 s or
/reset
of the parameter number (parameter number flashes).
Press
for >3 s until SEr appears.
/reset
When releasing
, you are on the service level.
/reset
ESC
to return to the selection
CC1P7546en