Modulating Operation; 2-Stage Operation - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Building Technologies

13.2 Modulating operation

Actual value
Voltage
Off
DC 0 V
Ignition load
DC 1 V
Low-fire
DC 2 V
High-fire
DC 10 V
The values between low-fire and high-fire are interpolated in a linear manner.

13.3 2-stage operation

Actual value
Voltage
Off
DC 0 V
Stage 1
DC 5 V
Stage 2
DC 10 V
13.4 3-stage operation
Actual value
Voltage
Off
DC 0 V
Stage 1
DC 3 V
Stage 2
DC 5 V
Stage 3
DC 10 V
Basic documentation LMV37.4...
13 Load output X74 pin 3
Curvepoint
Display / output
value
---
Off
P0
10%
P1
20%
P9
100%
Curvepoint
Display / output
value
---
Off
P1
P1
P2
P2
Curvepoint
Display / output
value
---
Off
P1
P1
P2
P2
P3
P3