Revision History Of Lmv37.4 - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Software changes
Building Technologies

30 Revision history of LMV37.4

Software version V01.20
Optimizations regarding ACS410 (backup / restore)
Faster parameterization with AZL2 (3-stage)
Burner identification setting (entering the password)
Optimization: LMV37.4 hooks itself up in phase 38
Optimization: Cold setting via P0 (adoption P0  P1, correct CALC function)
Optimization: Delete history (acknowledgement upon completion)
Prepurging oil – activated / deactivated (parameter 262) for OEM level released
Setting range of pulse valency fuel meter (parameter 128) increased to 400
pulses per volume unit
New parameter 645 = configuration analog output
Software version V01.30
Optimization of phase manager (rectification of error 107)
Presetting of parameter 281 (time oil ignition) changed to long preignition (with fan)
Software version V01.40
Optimization: Modbus mode and operating mode are maintained when a reset is
made
Extension: Additional Modbus addresses (refer to Modbus Documentation A7541)
Extension: Actuator tolerance can be parameterized by OEM and read by the
heating engineer
Change: The heating engineer can set the time when valve proving takes place
Extension: Calculation of fuel throughput
Optimization: Plausibility check for continuous operation with ionization amplifier
Optimization: Separate diagnostic code in the event standardization has not been
successful due to an undefined operating mode
Optimization: Change of password without having to enter the currently valid
password
Extension: Restore of data set possible only when type references of LMV37.4 and
data set are identical
Optimization: Alarm in the event of start prevention after a fixed time of 5 seconds
Extension: Selection of POC function or Pressure switch-max
Software version V01.60
Optimization: Filtering of analog power output
Optimization: Plausibility check of ionization amplifier revised
Software version V01.70
Optimization: Final test sequence revised.
Software version V01.80
Optimization: Valve proving during shutdown after display error in operation
Optimization: Any valve proving aborted by Pressure switch-min during shutdown is
repeated with the next startup
Basic Documentation LMV37.4...
30 Revision history of LMV37.4
255/267
CC1P7546en
17.12.2018