Electronic Ratio Control; General; Behavior Outside The Operating Positions; Traveling Speed - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

104/267
Building Technologies

10 Electronic ratio control

10.1 General

Electronic ratio control is used to control the burner's actuators depending on burner
output. It is possible to connect 2 actuators and, optionally, 1 VSD.
Resolution is 0.1° with the actuators and 0.1% with the VSD. Output can be regulated in
increments of 0.1% in modulating mode and with a maximum of 3 stages in multistage
mode.
To reduce the electric power required for the actuators, they are never operated
simultaneously, but in successive order, or alternately.

10.2 Behavior outside the operating positions

Outside their operating positions, the actuators approach the different positions in
successive order.
The program phase determines the position to be approached.

10.2.1 Traveling speed

The running speed of the actuators is fixed at 5 seconds for a positioning angle of 90°
for SQM33.4, SQM33.5, and SQN1.
The speed is 10 seconds for a positioning angle of 90° for SQM33.6.
The SQM33.7 requires 17 seconds for a positioning angle of 90°.
The ramp speed of the VSD can be adjusted separately for higher and lower speeds.
No.
Parameter
522
Ramp up
523
Ramp down
The setting also applies to the operating position (refer to chapter Operating position).

10.2.2 Home position

This position is approached in the Home run (10), Standby (12) and Lockout position
(00) phases.
The position can be set via the following parameters:
Parameter
Actuator
501.00
Idle position fuel actuator
502.00
Idle position air actuator
503.00
Idle speed VSD
Basic documentation LMV37.4...
10 Electronic ratio control
CC1P7546en
17.12.2018