Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of
small to medium capacity, operation, with or without fan in intermittent (26 pages)
Burner management system for forced draft burners with the main functions (39 pages)
Summary of Contents for Siemens LME7 Series
Page 1
LME7… Burner control Basic Documentation The LME7 and this Basic Documentation are intended for use by OEMs which integrate the burner controls in their products. Software version 02.00 Building Technologies CC1P7105en 17.04.2018...
Page 2
Supplementary documentation Type of documentation Product type Documentation number User Documentation PME71.111 A7105.1 PME71.112 User Documentation A7105.2 PME71.401 User Documentation A7105.3 PME71.402 User Documentation A7105.4 PME71.901 User Documentation A7105.5 PME72.521 *) User Documentation A7105.11 PME72.541 *) User Documentation A7105.12 PME73.810 User Documentation A7105.21 PME73.811...
Page 4
4.12 Flame supervision ..................31 4.12.1 Ionization probe ..................... 31 4.12.2 Flame detector QRA2 / QRA4 / QRA10 ............33 Dimensions ....................34 Function ......................35 Preconditions for burner startup ..............35 Undervoltage ....................35 Controlled intermittent operation ..............35 Control sequence in the event of fault ............
Page 5
11.4.2 Analog input terminal X65 ................49 11.4.3 Selection source preset output analog / 3-position step input (parameter 654) ..................... 49 11.4.4 Actuator output terminal X2-09 ..............49 11.4.5 Setting the maximum running time of the actuator (parameter 259 / 260 timeout) ....................
Page 6
13.7.2 Display of service values ................67 13.7.2.1. Error history ....................67 13.7.2.2. Mains voltage ....................67 13.7.2.3. Intensity of flame ................... 67 13.7.2.4. End of service level ..................67 13.8 Parameter level ..................... 68 13.8.1 Entering the password ................... 69 13.8.2 Changing the heating engineer's password...........
Page 7
15.8 Manual restore ..................... 102 15.8.1 Errors during the restore process ..............103 15.8.2 Reset ......................103 List of figures ....................106 7/106 Building Technologies Basic Documentation LME7… CC1P7105en Contents 17.04.2018...
The LME7 are safety devices! Do not open, interfere with or modify the unit. Siemens does not assume responsibility for damage resulting from unauthorized interference! Additional safety notes contained in other chapters of this document must be observed as well! ∂...
To ensure safety and reliability of the LME7 system, the following points must also be observed: Condensation and ingress of humidity must be avoided. Should such conditions occur, make sure that the unit will be completely dry before switching on again! If not observed, there will be a risk of electric shock Static charges must be avoided since they can damage the unit’s electronic components when touched.
Since the BCI has no safe separation from mains voltage, the signal cable AGV50 between LME7 and AZL2, or LME7 and OCI410, must conform to certain specifications. Siemens has specified the signal cable AGV50 for use under the burner hood (see Technical data). When using signal cables of other manufacture, Siemens’...
Electrical connection of flame detectors It is important to achieve practically disturbance- and loss-free signal transmission: ∂ Never run the detector cable together with other cables – Line capacitance reduces the magnitude of the flame signal – Use a separate cable ∂...
Commissioning notes Prior to commissioning the system, the following points must be checked: ∂ Correct assignment of the valves to the valve outputs at the LME7 ∂ Correct setting of the time parameters, especially the safety and prepurge times ∂ Correct functioning of the flame detector in the event of loss of flame during operation (including the response time), with extraneous light, during the prepurge time and, when there is no establishment of flame, at the end of the ignition safety...
The electrical connections of the LME7 and the PME7 comply with the requirements of EN 60335-2-102. EAC Conformity mark (Eurasian Conformity mark) ISO 9001:2015 ISO 14001:2015 OHSAS 18001:2007 China RoHS Hazardous substances table: http://www.siemens.com/download?A6V10883536 Only AC 120 V versions 13/106 Building Technologies Basic Documentation LME7... CC1P7105enr 1 Safety notes 17.04.2018...
1.7 Lifetime Burner controls have a designed lifetime* of 250,000 burner startup cycles which, under normal operating conditions in heating mode, correspond to approx. 10 years of usage (starting from the production date given on the type field). This lifetime is based on the endurance tests specified in standard EN 298 and the table containing the relevant test documentation as published by the European Association of Component Manufacturers (Afecor) (www.afecor.org).
The device may only be used on the applications described in the technical documentation and only in connection with devices or components from other suppliers that have been approved or recommended by Siemens. The product can only function correctly and safely if shipped, stored, set up and installed correctly, and operated and maintained as specified.
System makeup / function description The LME7 is a microprocessor-based burner control with matching system components for the control and supervision of forced draft burners of medium to high capacity. LME7 are used for the startup and supervision of 1- or 2-stage forced draft burners in intermittent operation.
The LME7 system components (display and operating unit AZL2) are connected directly via BCI to the LME7 basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network. For intermittent operation in connection with the LME7, the ionization probe and, optionally, the flame detector QRA2, QRA4 or QRA10 can be used.
Type summary 3.1 Burner controls Parameterized burner control for the supervision of multistage or modulating oil/gas forced draft burners and atmospheric burners of medium to higher capacity, in intermittent operation. With controlled air damper control. Article no. Type ● ● Mains voltage AC 120 V ●...
3.2 Program module 3.2.1 PME7 with mains voltage AC 120 V Program module for LME7 with program sequences oil or gas burners for basic unit LME7. Example: Article no. Type ● ● ● ● ● ● ● ● ● ● ●...
3.2.2 PME7 with mains voltage AC 230 V Example: Article no. Type ● ● ● ● ● ● ● ● ● ● ● ● ● ● Mains voltage AC 230 V ● ● ● ● ● For use with LME71.000A ●...
Die-cast aluminum housing with a 1 in. mounting coupling and connection facility for cooling air. See Data Sheet N7712 Ionization probe Flame detector for Siemens burner controls, for supervision of gas flames. To be provided on site 21/106 Building Technologies Basic Documentation LME7...
3.5 Actuators SQN3 Electromotoric actuators for air dampers and control valves of oil and gas burners of small to medium capacity. Holding torque / running time 0.8 Nm / 4.5 s until 3 Nm / 30 s See Data Sheet N7808 SQN7 Electromotoric actuators for air dampers and control valves of oil and gas burners of small to medium capacity.
3.8 Connector sets for LME7 AGG3.710 Article no.: BPZ:AGG3.710 Connector set complete for LME7 RAST5 and RAST3.5 Example: Single packs Terminal X5-03 See List or parts C7105 (74 319 0642 0) AGG3.720 Article no.: BPZ:AGG3.720 10 standard connector sets complete for LME7 RAST5 and RAST3.5 Single packs The several connectors are delivered into bags to 10 pieces...
3.9 Service- tools OCI410 Article no.: BPZ:OCI410 Interface between burner control and PC Facilitates viewing, handling and recording setting parameters on site in connection with the ACS410 software See Data Sheet N7616 ACS410 Article no.: BPZ:ACS410 PC software for setting the parameters and for visualizing the burner controls See Software Documentation J7352 24/106...
Technical data 4.1 Basic unit LME7 Mains voltage AC 120 V AC 230 V General Mains frequency 50/60 Hz 50/60 Hz External primary fuse Max. 6.3 A (slow) Max. 6.3 A (slow) Power consumption <10 W, typical <10 W, typical Safety class I with parts according to II and III to DIN EN 60730-1...
4.2 Terminal rating Inputs Mains voltage: Input current depending on the operating state of the unit Under voltage 120 V 230 V Mains Mains ∂ Safety shutdown from the operating ≤AC 75 V ≤AC 165 V position takes place should mains voltage drop ∂...
4.3 Terminal rating Outputs Total contact loading: ∂ Rated voltage AC 120 V AC 230 V 50/60 Hz 50/60 Hz ∂ Unit input current terminal X3-04 Max. 5 A Max. 5 A (safety loop) from: - Fan motor contactor - Ignition transformer - Fuel valves Individual contact loading: Fan motor X2-01 pin 3...
4.4 Cable lengths Mains supply line Max. 100 m (100 pF/m) Display, BCI For use under the burner hood or in a control panel Max. 1 m (100 pF/m), unshielded Load controller X5-03 Max. 30 m (100 pF/m), unshielded Safety Loop Max.
4.7 RAST5 connector ′4 N Mechanical data Insertion force / contact ″1 N Withdrawal force / contact Tightening torque / screw 0.5 Nm in accordance with DIN EN 60335-1 Contacting with flat pin connector 6.3 x 0.8 mm in accordance with DIN EN 46244 Male multipoint connector to RAST5 standard...
4.11 Environmental conditions Storage DIN EN 60721-3-1 Climatic conditions Class 1K3 Mechanical conditions Class 1M2 Temperature range -40...+70 °C Humidity <95% r.h. Transport DIN EN 60721-3-2 Climatic conditions Class 2K3 Mechanical conditions Class 2M2 Temperature range -40...+70 °C Humidity <95% r.h. Operation DIN EN 60721-3-3 Climatic conditions...
4.12 Flame supervision 4.12.1 Ionization probe No-load voltage at terminal ionization AC 300 V probe (terminal X10–05 pin 2) Warning! ∂ The ionization probe must be protected against electric shock hazard! ∂ When monitoring ionization currents in earth-free mains, connect terminal X10-05 pin 1 to burner ground Short-circuit current Max.
Page 32
Ionization probe Measuring circuit for detector current measurement LME7... X10-05/2 X10-05/1 Figure 4: Measuring circuit for ionization probe Legend Electrolytic condenser 100...470 µF; DC 10...25 V Ionization probe Microammeter Ri max. 5,000 ς Warning! Simultaneous operation of QRA and ionization probe is not permitted! If not observed, there is a risk of impairment of safety functions.
4.12.2 Flame detector QRA2 / QRA4 / QRA10 Caution! If flame detectors QRA2 / QRA4 / QRA10 are used for flame supervision with the LME7, it must be ensured that the burner control is permanently connected to power (conforming to EN 298), thus enabling the system to detect flame detector failures during startup and shutdown.
Function 6.1 Preconditions for burner startup ∂ Burner control must be reset ∂ All contacts in the line are closed, there is a request for heat ∂ No undervoltage ∂ Air pressure switch or POC must be in its no-load position, or Dbr1 is connected to terminal X2-02 (depending on program sequence) ∂...
6.4 Control sequence in the event of fault If a non-alterable lockout occurs, the outputs for the fuel valves, the burner motor and the ignition equipment are always immediately deactivated (<1 second). Cause Response Mains voltage failure Restart Voltage below undervoltage threshold Safety shutdown Voltage above undervoltage threshold Restart...
6.6 Limitation of repetitions Depending on program module, see User Documentations. 6.6.1 Repetition in case of loss of flame If the flame is lost during operation, a maximum of 1 repetition per controlled startup can be performed via the control thermostat or pressurestat, or else a non-alterable lockout will be initiated.
Operation, indication, diagnostics 7.1 Operation The lockout reset button (info button) is the key operating element for resetting the burner control and for activating / deactivating the diagnostics functions. Yellow The multicolor signal lamp is the key indicating element for visual diagnostics.
7.3 Diagnostics of cause of fault After a non-alterable lockout, the red fault signal lamp (LED) lights up. In that condition, visual diagnostics of cause of fault according to the error code table can be activated by pressing the lockout reset button (info button) for more than 3 seconds.
Page 40
Error code table Red blink code of fault signal lamp Possible cause 2 x blinks No establishment of flame at the end of the safety time - Faulty or soiled fuel valves - Faulty or soiled flame detector - Poor adjustment of burner, no fuel - Faulty ignition equipment 3 x blinks Air pressure switch faulty...
10 Basic unit 10.1 Description of inputs and outputs Note! Β This section covers the key features of the basic unit’s inputs and outputs. For exact use of the inputs and the activation of outputs, see chapter Sequence diagrams. LME... Flame signal input and flame detector terminal QRA...
10.2 Digital input 10.2.1 Safety Loop terminal X3–04 pin 1 and 2 Input for connection of the safety loop. When any of the series-connected contacts included in the loop opens, power supply to the fuel valves, the fan and the ignition equipment is instantly cut.
10.2.3 Air pressure switch terminal X3–02 Input for connection of an air pressure switch. Air pressure is anticipated when the fan is switched on. If there is no air pressure signal, the system initiates lockout. The air pressure switch must have an NO contact. If no air pressure switch is required (e.g.
Multistage or modulating mode with actuator 11.1 Relevant parameters Parameter Meaning Minimum output control step Opening time of actuator (timeout) Closing time of actuator (timeout) Analog input (feedback potentiometer ASZxx.3x required) 0 = 3-position step input 1 = DC 0...10 V 2 = 0...135 ς...
11.1.2 Connection diagram for load controller Β Note! The connection diagram shown is merely an example which must be verified in the individual case depending on the application! PME7 0-135 Figure 16: Connection diagram for load controller 11.2 Actuators The LME7 has terminals for the connection of electromotoric actuators for the control of air dampers and regulating dampers of oil and gas burners.
11.4 Load controller inputs 11.4.1 3-position step input terminal X5-03 The load controller input is valued by making a 2-out-of-3 section. This means that to trigger a control action via the actuator outputs, an ON or OFF signal must be identified within at least 2 successive cycles.
11.5 Multistage / modulating mode via 3- position step input terminal X5-03 The signal time of a control pulse is a minimum of 147 ms. 11.5.1 Maximum possible resolution The maximum possible resolution via 3-position step input terminal X5-03 is calculated according to the following formula: Working range in angular degrees x 0.147 s ---------------------------------------------------- = maximum possible resolution in angular degree...
11.7 Setting the minimum power control step (dead band) (parameter 123) in modulating mode via analog input signal terminal X65 The minimum output control step must be greater than or equal to the percentage proportion of the maximum resolution of the entire modulation range and, depending on the actuator’s running time (protection against hunting).
User limitations / application examples Application Typical resolution Typical modulation range Actuator control Controller with via LME73 - pulse lengths min. 150 ms 1 : 30 / 1 : 50 3 position control - approx. 0.5° LME73 - with 30 s running time For boiler and 0...90°...
If not observed, there will be a risk of electric shock. If you have any other questions relating to the unit, please contact your heating engineer or get in touch with any of the Siemens addresses given in this Basic Documentation.
Operation via AZL2 13.1 Description of the unit / display and buttons Function and operation of versions AZL21 and AZL23 are identical. /reset h min s Figure 17: Description of the unit / display and buttons Button Function Buttons A and F: Parameterized function - For switching to parameter setting mode P (press simultaneously)
13.2 Meaning of symbols on the display Fault status message Flame present Valve controlled Ignition controlled Fan motor controlled Oil preheater on Heat request from controllers Parameter setting mode Info mode Service mode h min s Actuator closing Actuator opening Unit of current display Figure 18: Meaning of display 13.3...
13.4 Operation Warning! Any changes to parameters and settings are only set and saved in the basic unit’s onboard memory. To save the modified settings to the program module PME7, backup must be triggered manually. If this is not observed, there is a risk of loss of safety functions. ↑...
List of phase display (display depending on program) Β Note! Display depends on program module, see User Documentations! Phase number Function AZL2 display Standby Standby, waiting for heat request Ph08 Power ON / test phase (e.g. detector test) Startup Ph21 Safety valve ON, air pressure switch test / POC test (timeout / locking after 5 seconds), actuator opens in low-fire position / CLOSE position Ph22...
13.4.1.3. Display of operating position Display oP: P1 means stage 1. Display after oP is unit-specific. h min s Display oP: P2 means stage 2. Display after oP is unit-specific. Display oP: means modulating operation. Display after oP: is unit-specific. Display shows the relative value of the actual position of actuator (51).
13.4.1.4. Fault status messages, display of errors and info Display of errors (faults) with lockout Display shows Loc:. The bar under the fault status message appears. Unit is in the lockout position. The current error code is displayed (see chapter Blink h min s code table).
13.5 Menu-driven operation 13.5.1 Assignment of levels The various levels can be accessed via different button combinations. The parameter level can only be accessed by entering a password. Normal display >1 s /reset Operate >8 s Info level /reset >3 s <8 s /reset automatic...
13.6 Info level 13.6.1 Display of info level Press until InFo appears. /reset /reset 1…3 s When releasing , you are on the info level. /reset The info level displays information about the basic unit and operation in general. Β Note! On the info level, you can press to display the next or the previous parameter.
13.6.2 Display of info values 13.6.2.1. Identification date The identification date described below corresponds to the creation date for the program sequence and cannot be changed by the user. On the left, parameter 102: is displayed blinking. On the right, ._._ is displayed. h min s Example: 102: ._._ …...
13.6.2.3. Identification of burner On the left, parameter 113: is displayed blinking. On the right, ._._ appears. Example: 113: ._._ h min s Press for 1…3 seconds to display the /reset burner’s identification. /reset Factory setting: - - - - - - - - 1…3 s h min s Example: 3...
13.6.2.4. Number of startups resettable Β Note! Can be deleted for service (see chapter Parameter list)! On the left, parameter 164: is displayed blinking. On the right, characters ._._ appear. Example: Parameter 164: ._._ h min s Pressing the button (1 …...
13.6.2.5. Total number of startups On the left, parameter 166: is displayed blinking. On the right, characters ._._ appear. Example: Parameter 166: ._._ h min s … 3 seconds) and Pressing the button (1 /reset releasing it when ._._ flashes displays the total number of startups.
13.7 Service level The service level is used to display information about errors including the error history. Β Note! When on the service level, you can press to display the next or the previous parameter. Instead of pressing , you can also press for <1 second.
13.7.2 Display of service values 13.7.2.1. Error history See Parameter with index, with or without direct display / example of parameter 701 Error history. Β Note Can be deleted for service (see chapter Parameter list)! Refer to chapter Error code list! 13.7.2.2.
The OEM is obliged to mark the unit accordingly and to include at least the list of device parameters and settings in the burner’s documentation. Siemens also recommends attaching an additional mark on the LME7 in the form of an adhesive label. According to EN 298, the label should be easy to read and wipeproof.
13.8.1 Entering the password Note! Β The OEM password must consist of 5 characters, that for the heating engineer of 4 characters. Press button combination to display CodE. >1 s h min s When releasing the buttons, 6 bars appear the first of which blinks.
Page 70
As a confirmation of correct entry, PArA appears for a maximum of 2 seconds. h min s Β Note: For the entry of passwords or burner IDs, the following numerals and letters can be used: 70/106 Building Technologies Basic Documentation LME7... CC1P7105en 13 Operation via AZL2 17.04.2018...
13.8.2 Changing the heating engineer's password Note: Β For the OEM to change the heating engineer’s password, c: demands entry of the OEM password! Press button combination to display 000: Int. >1 s Pressing the button takes you to parameter /reset 041 heating engineer's password.
Page 72
Pressing the button takes you to /reset parameter 041 heating engineer's password. Continue in the parameter End of the parameter level level to the next parameter –End- group 100: 72/106 Building Technologies Basic Documentation LME7... CC1P7105en 13 Operation via AZL2 17.04.2018...
13.8.3 Changing the OEM's password Parameter 042: blinks. Press to go to level c: for password changes. /reset Letter c: for confirmation appears blinking. Proceed as described in section Entering the password and enter the former password. After entry of the last character, the password must be /reset confirmed by pressing /reset...
13.8.4 Backup Parameter 000: blinks. Display: Parameter 000: blinks, display Int does not /reset Press for parameter group 041. /reset Display: Parameter 041: blinks, display ._._ does not Press for parameter 060. Display: Parameter 060. blinks, index 00: and value 0 do /reset Press for parameter rEStorE.
Page 75
Press for value 1. Display: Value 1 blinks /reset Press to activate the backup process. /reset Display shows run After approx. 3 seconds (depending on the duration of the program sequence), the displays shows bAC End and <3 s signals the end of the backup process. Display: bAC End It will now be displayed for 2 minutes, or can be finished by pressing the button...
13.8.5 Restore Parameter 000: blinks. Display: Parameter 000: blinks, display Int dos not /reset Press for parameter group 041. /reset Display: Parameter 041: blinks, display ._._ does not. Press for parameter 060. Display: Parameter 060. blinks, index 00: and value 0 do not.
Page 77
/reset Press to activate the restore process. /reset Display shows run After approx. 3 seconds (depending on the duration of the program sequence), the displays shows rSt End and <3 s signaled the end of the restore process. Display: rSt End It will now be displayed for 2 minutes, or can be finished by pressing the button /reset...
13.9 Operating variants of the parameters The parameters stored in the burner control LME7 can be displayed and changed on the parameter level. Press button combination to display 000: Int. With , select the parameter group 100: >1 s PArA. With , select the parameter group 200: PArA.
Page 79
Alternative 1: Discard the change! h min s Alternative 2: Adopt the value! /reset Press to return to editing mode. /reset The value set will be adopted. Note: To detect display errors, the value appears one h min s place shifted to the right. Display: Value 3.822 h min s Back to the previous...
13.9.2 Parameters without index, with no direct display 13.9.2.1. Example of parameter 224 (specified time air pressure switch) on the parameter level Press for specified time for air pressure signal. Display: Parameter 224: blinks, characters h min s ._._ do not. /reset Press for editing mode.
Page 81
Alternative 1: Discard the change! h min s Alternative 2: Adopt the change! /reset Press to return to editing mode. /reset The value set will be adopted. Note: To detect display errors, the value is shown again, h min s but shifted one place to the right.
13.9.3 Parameters with index, with or without direct display 13.9.3.1. Example of parameter 701: Actual error on the service level See chapter Error code list! Press to select parameter 701. Display: Parameter 701. blinks, index 00: and error 4 do not.
Page 83
Press to select the index. .02 = MMI phase to the time of fault Example: h min s Parameter 701., index 02:, Phase 02 = safety shutdown To the next index Press to select the index. .03 = power value to the time of fault Example: h min s Parameter 701., index 03:, power value 60%...
Page 84
Press to return to the parameter level. Display: Parameter 701. blinks, index 01: and diagnostic code 4 do not. h min s To the next older error ▪ ▪ ▪ Parameters cover the period back to the last error since deletion of the history (max.
14 Error code list with operation via external AZL2 display Β Note: Display depends on program module, see User Documentations! Error code Clear text Possible cause - Faulty or soiled fuel valves No establishment of flame at the end of safety - Faulty or soiled flame detector time Loc: 2...
Page 86
Error code Clear text Possible cause - After the prepurge speed was reached, the minimum PWM prepurge speed was undercut (parameter 675.00) or ... Loc: 225 PWM fan faulty - After reaching the ignition load speed, the maximum ignition load PWM (parameter 675.01) was exceeded Parameterization error: - Speed low-fire >...
Operation via internal LED 15.1 Description of display and buttons Figure 22: Description of display and buttons Button Function Button A - Display preset output - In lockout position: Power value to the time of fault Info and Enter button - Reset in the event of fault, changeover visual diagnostic of the cause of fault (see chapter Diagnostics of cause of fault ) - button...
15.2 Normal display Normal display is the standard display in normal operation. 15.2.1 Display in standby mode Unit is in standby mode. 15.2.2 Display during startup / shutdown 15.2.2.1. Display of program phases The unit is in Phase 21. The individual program phases are displayed in accordance with the program sequence.
15.2.2.2. List of phase display Β Note: Display depends on program module, see User Documentations! Phase number Function AZL2 display Standby Standby, waiting for heat request Power ON / test phase (e.g. detector test) Startup Yellow Safety valve ON, air pressure switch test / POC test (timeout / locking after 5 seconds), actuator opens in low-fire position / CLOSE position Yellow Fan motor ON and air pressure switch test / settling time...
Page 90
Phase number Function AZL2 display Waiting phases (start prevention / safety shutdown phases) Red / yellow flashing Undervoltage Yellow Safety loop open ↑ Safety shutdown, followed by a non-alterable lockout with interlocking Red / green flashing Extraneous light on burner startup (timeout / locking after 30 seconds) Yellow Pressure switch-min open ↑...
15.2.3 Display of operating position Display oP1 means stage 1. Display after oP is unit-specific. The signal lamp blinks green. 15.3 Special functions 15.3.1 Manual lockout Press simultaneously with any other button. Basic unit changes from any operating position Alternately directly to lockout.
15.4 Fault status messages, display of errors 15.4.1 Display of errors (faults) with lockout Display shows alternately Loc and 4. Unit is in the lockout position. Alternately The current error code is displayed and the signal lamp is blinking red. Example: Error code 4 Press for display of the phase, where the fault...
15.4.2 Display of flame current ION or QRA Β Note: This display is only possible in operating mode or standby! Press for display of the flame signal amplifier. Signal lamp blinks green. Display shows FL.1. When pressing (1…3 seconds), the flame signal current is displayed.
15.4.4 Display of preset output Note: Β Display is possible only when … ∂ in operating mode or standby, ∂ program sequence for modulating operation via analog preset output. Press for display of the relative current position of the actuator. Signal lamp blinks green.
15.5 Manual adjustment (depending on program module) 15.5.1 Position of actuator or speed of PWM fan in modulating operation with analog signal Note: Display is possible only when … Β ∂ in operating mode or standby, ∂ program sequence for modulating operation via analog preset output and with connected actuator with potentiometer for position feedback to the LME7 Press for the relative current position of the actuator or...
Page 96
Press for >3 seconds to display alternately LoA and The relative value 41 of the current position or current speed is displayed. Actuator position 0° Current speed 0 ς potentiometer value = 0 rpm = 0 display 0% display Current speed corresponds Alternately Actuator position high-fire to the rated load speed =...
Page 97
Note: ∂ When the program phase (e.g. P10 - shutdown) changes during manual adjustment, the display blinks Β ∂ Manual adjustment mode remains active until Escape switches the basic unit back to normal operation or until the basic unit is reset via mains ON/OFF. This means that in the case of a new heat request and after startup, the actuator or the PWM fan is driven to the position or speed of the manually preset value 97/106...
15.6 First startup with a new program module or in case of replacement of program module Display shows alternately rSt and PrC. Alternately Display shows the replacement of the program module. Signal lamp blinks red once and yellow twice alternately. Press for >3 seconds to start data download from the program module.
Page 99
Press for >1 second to reset the unit. Display: OFF >1 s Warning! On first startup or after exchange of the program module, the sequence of functions and parameter settings must be checked upon completion of the restore process ↑ See chapter Operation via AZL2 / first startup, restore ↑...
15.7 Manual backup Press simultaneously for >1 second (Escape) to start a manual backup process. Parameter PrC appears. Display: PrC >1 s Press for parameter bAC. Display: bAC 1…3 s run appears during download (backup process) of the program sequence. Display shows alternately End and bAC.
15.7.1 Error during backup process Display shows alternately bAC and Er3. Alternately For meaning of a possible cause, see chapter Error code list with operation via internal LED. Β Note: During backup, all settings and parameters are transferred from the basic unit’s memory to the memory of the program module.
15.8 Manual restore Press simultaneously for >1 second (Escape) for starting the manual restore process. Parameter PrC appears. Display: PrC >1 s Press for parameter rSt. Display: rSt 1…3 s run appears during download (restore process) of program sequence. Display shows alternately End and rSt. Alternately Display shows the end of data exchange.
15.8.1 Errors during the restore process Alternately with Display shows alternately rSt and Er1, Er2 or Er3. or with For meaning of a possible cause, see chapter Error code list with operation via internal LED. or with Β Note: During the restore process, all settings and parameters are written from the program module to the basic unit’s onboard memory.
Page 104
Index Mains voltage ......69 AGG9 Special functions ....... 57 Connection diagram....44 Manual lockout ......57 AZL2 Description of the unit / display Basic unit ......... 46 and buttons ........ 56 Air pressure switch X3-02 ..48 Error code list ......87 Description of inputs and outputs ....
Page 105
Position of actuator or speed of Maximum possible resolution 52 PWM fan in modulating Multistage or modulating mode operation with analog signal Relevant parameters ....49 ..........97 Setting the minimum power Manual backup ......102 control step in modulating mode Error during backup process 103 via analog input signal X65 ..