Legend To The Sequence Diagrams - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

88/267
Building Technologies

7.7.8 Legend to the sequence diagrams

Note
Not all phases, times, indices, abbreviations and symbols appear in the
individual sequence diagrams or are needed there!
Phase numbers
00
Lockout phase
02
Safety phase
10
Home run
12
Standby (stationary)
22
Fan motor = ON, safety valve = ON
Air damper  pre purge position
24
30
Prepurging
Fan  ignition speed
35
Air damper  ignition position
36
38
Preignition ignition = ON
39
Test pressure switch-min
40
Fuel valve = ON
42
Ignition = OFF
44
Interval 1
50
Second safety time
52
Interval 2
60
Operation 1 (stationary)
Operation 2 (air damper  low-fire position)
62
64
Switching back to pilot: Modulation to ignition load
65
Switching back to pilot: Interval 2 waiting time
66
Switching back to pilot: Reactivation of ignition + pilot
67
Switching back to pilot: Shutdown of main valves
68
Switching back to pilot: Pilot mode waiting phase
69
Switching back to pilot: Pilot mode waiting phase for burner startup
70
Afterburn time
Fan  postpurge speed
71
Air damper  Rated load position
72
74
Postpurge time
78
Postpurge time
Fan  standby speed
79
80
Evacuation of test space
81
Test time atmospheric pressure
82
Filling of test space
83
Test time gas pressure
90
Gas shortage waiting time
Valve proving is performed depending on the parameter settings:
Simultaneously with the prepurge time and/or the afterburn time.
Times
TSA1
1st safety time
TSA2
2nd safety time
t1
Prepurge time
t3
Postpurge time
t8
Postpurge time
t13
Afterburn time
t44
Interval 1
t52
Interval 2
Basic documentation LMV37.4...
7 Basic unit LMV37.4
CC1P7546en
17.12.2018