Siemens LMV37.4 Series Basic Documentation page 246

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Error
Diagnostic code
code
Valency 1
Bit 1
Valency 2..3
Bit 2
Valency 4..7
85
#
0
1
246/267
Building Technologies
Meaning for the LMV37.4
Fuel actuator: Curve too steep in terms of ramp rate
Air actuator: Curve too steep in terms of ramp rate
Referencing error ones actuators
Referencing error of fuel actuator
Referencing error of air actuator
Basic documentation LMV37.4...
29 Error code list (all LMV2 types / LMV3 types)
Recommended measures or causes
(parameter 544).
1.
Modulating operating ramp 32 seconds
Curve slope max. 10% for LMV37.4 ramp of 20 seconds (20% for 10 seconds or 40% for 5
seconds)
2.
Modulating operating ramp 48 seconds
Curve slope max. 10% for LMV37.4 ramp of 30 seconds (20% for 15 seconds or 30% for 10
seconds)
3.
Modulating operating ramp 64 seconds
Curve slope max. 10% for LMV37.4 ramp of 40 seconds (20% for 20 seconds or 40% for 10
seconds)
→ Between the ignition point (P0) and the low-fire point (P1), the speed change in modulating
mode may be a maximum of 40%, independent of the LMV37.4 ramp.
4.
Setting of the VSD ramp must be about 20% shorter than the ramps in the LMV37.4
(parameters 522 and 523)
Check position differential between the curvepoints and the modulating operating ramp setting
(parameter 544).
1.
Modulating operating ramp 32 seconds
The slope of the curve may be a maximum position change of 31° (15° for SQM33.6 and 9° for
SQM33.7) between 2 curve points in modulating mode.
2.
Modulating operating ramp 64 seconds
The slope of the curve may be a maximum position change of 62° (30° for SQM33.6 and 18°
for SQM33.7) between 2 curve points in modulating mode.
Check position differential between the curvepoints and the modulating operating ramp setting
(parameter 544).
1.
Modulating operating ramp 32 seconds
The slope of the curve may be a maximum position change of 31° (15° for SQM33.6 and 9° for
SQM33.7) between 2 curve points in modulating mode.
2.
Modulating operating ramp 64 seconds
The slope of the curve may be a maximum position change of 62° (30° for SQM33.6 and 18°
for SQM33.7) between 2 curve points in modulating mode.
Referencing of fuel actuator not successful.
Reference point could not be reached.
1.
Check the setting of the actuator type (parameter 613.0 or 614)
2.
Check to see if actuators have been mixed up
3.
Check to see if actuator is locked or overloaded
Referencing of air actuator not successful.
Reference point could not be reached.
CC1P7546en
17.12.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents