Siemens LMV37.4 Series Basic Documentation page 258

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

258/267
Building Technologies
Software version V03.10
Optimization: If power supply fails during the restore process, the data set can be
repaired by starting a new restore process (since the backup / restore option is not
yet available with V03.00 because there is no suitable AZL2, this effect cannot
occur)
Optimization: When making a reset via the AZL2, an incomplete reset occurred in
very rare cases (display showed RESEt, but reset was not triggered)
Optimization: The time ascertained by the loss-of-flame test was 0.2 seconds too
long
Optimization: Reduced detection of undervoltage when fan motor is started in phase
22 (when a single-phase motor and the LMV37.4 were powered via the same
phase, undervoltage detection could occur on startup; in that case, the LMV37.4
was not operated as specified)
Optimization: Better overview through text changes of groups 200 = PAr0,
300 = PAr1 and 600 = ACtr on the parameter menu (initially PArA), and hiding of
unused parameters after selection of fuel train/operating mode
Optimization: Control of the fan output during standardization (standby) for using a
release contact via an external relay at the fan's output
Optimization: Curve setting invalid (OFF UPr) after new / further standardization
Optimization: To shorten the startup time, there is no referencing when postpurging
is aborted via load controller ON (direct start)
Automatic return travel of the SQN1 at the lower internal stop
Parameter on Siemens level
Longer ignition off time during the first safety time (increased from 0.4 to 0.6
seconds) to prevent wrong error diagnostics in connection with QRA2 (C:7 in place
of C:2)
Software version V03.30
Extension: Display of intensity of flame when setting the curves
Optimization: Display and diagnostics of changing start preventions
 Optimization: No unplausible relay setpoint (error C:99 D:3) when starting
standardization, alarm in case of start prevention and load controller ON signal
Optimization: No VSD standardization with pneumatic fuel-air ratio control
Optimization: Referencing in connection with direction of rotation Right and home
position 90°
Software version V03.40
Extension: Supports SQM33.6 or SQM33.7
Extension: Postpurging in the lockout position
Extension: Heavy oil operating modes
Optimization: Shutdown of VSD control when burner flange / safety loop is open
Optimization: Minimum setting for prepurge time: 5 seconds
Extension: Switching back to pilot function
Optimization: Standstill supervision of the VSD can be switched off in standby mode
Extension: No flame at the end of safety time repetition counter, adjustable air
pressure failure (OEM), heavy oil direct start (SO)
Extension: Air pressure supervision in operation with pneumatic fuel-air ratio control
can be switched off (OEM)
Extension: VSD ramp time increased to 40 seconds
Extension: Modbus data points
127 = Fuel 0 operating mode (parameter 201)
128 = Fuel 1 operating mode (parameter 301)
129 = Switching back to pilot cycle counter (parameter 176)
Basic Documentation LMV37.4...
30 Revision history of LMV37.4
CC1P7546en
17.12.2018