Optional Internal Checks - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Building Technologies
No.
Parameter
Behavior if analog input is invalid (4...20 mA) 
0 = deactivate default output low-fire / trim function (with warning message) 
204
1 = safety shutdown + startup prevention
2 = deactivate default output low-fire / trim function (without warning message)
Activation trim function
0 = inactive
1 = active
530
2 = active (including test function for analog input)
3 = active (including ignition speed)
4 = active (including ignition speed and analog input test)
547
Lower range limit trim function
548
Upper range limit trim function
549
Damping factor for trim function (based on low-fire)
550
Delay time / wait time for trim function after entering phase 60
551
Wait time until response with active trim limitation
Behavior if maximum trim limitation time is exceeded
0 = warning message only (trim impact remains active)
552
1 = warning and deactivation of the trim function
2 = shutdown
12.15.2

Optional internal checks

The LMV37.4 has various settings and monitoring options to ensure that the trim
function runs correctly and error-free. The external control unit and control section are
used here in places. The OEM is responsible for implementing the necessary measures
for fulfilling the local requirements.
Plausibility check for the curve setting
When the trim function is activated, the LMV37.4 carries out permanent supervision of
the speed curve. In order to cover the desired range with the trim function, a sufficient
reserve must be available in the curve setting (e.g. upper trim limit 10%  90%
maximum curve setting). Otherwise, it wouldn't be possible to carry out the desired trim
correction, as the speed would be limited by the minimum or maximum limitation.
Error-
Diagnostic code Meaning for the LMV37.4
code
155
#
0..9
20..29
40..49
60..69
Basic documentation LMV37.4...
12 Fan control
Trim function: Invalid curve setting VSD / PWM fan
Minimum value VSD curve fall below
Maximum value VSD curve exceeded
Fuel 1: Minimum value VSD curve fall below
Fuel 1: Maximum value VSD curve exceeded
143/267
CC1P7546en
17.12.2018