Valve Proving With Separate Pressure Switch X9-04 - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

P
P
min
LT
P LT
Figure 32: Valve proving with separate
pressure switch
Building Technologies
It must be ensured that the 2 test times are correctly set. It is to be checked whether the
gas required for the test may be fed into the combustion chamber (on the relevant
application). The test times are safety-related. After a reset and in the case of aborted or
prevented valve proving, the unit performs valve proving on the next startup (only when
valve proving is activated). Prepurging with valve proving is active during the startup
phase, even if it was deactivated.
Examples of aborted valve proving:
If the safety loop or the start prevention input for gas (containing pressure switch-min)
opens during valve proving.
Valve proving – calculation of leakage rate
(P G - P w )
V
t Test = 
P atm
Q Leck
Q
in l/h
Leck
P
in mbar
G
P
in mbar
W
P
in mbar
atm
V
in l
t
in s
Test

7.5.3 Valve proving with separate pressure switch X9-04

Step 1: t80 – evacuation of test space.
Gas valve on the burner side is opened to bring the test space to
atmospheric pressure.
Step 2: t81 – test time atmospheric pressure.
When the gas valve has closed, the gas pressure in the test space must
not exceed a certain level.
Step 3: t82 – filling of test space.
Gas valve on the mains side opens to fill the test space.
Bild 410e/1010
Step 4: t83 – test time gas pressure.
When the gas valve has closed, the gas pressure in the test space must
not drop below a certain level.
Legend
t80
t81
t82
t83
V...
P LT
Pmin
Basic documentation LMV37.4...
7 Basic unit LMV37.4
3600
Leakage rate in liters per hour
Overpressure between the valves at the beginning of the test phase
Overpressure set on the pressure switch (normally 50% of the gas inlet
pressure)
Absolute air pressure (1013 mbar normal pressure)
Volume between the valves (test volume) including valve volume
and pilot pipe, if present (Gp1 mod)
Test time
Evacuation of test space (parameter 242)
Test time atmospheric pressure (parameter 243)
Filling of test space (parameter 244)
Test time gas pressure (parameter 245)
Fuel valve
Pressure switch – valve proving
Pressure switch-min
Input/output signal 1 (ON)
Input/output signal 0 (OFF)
Input permissible signal 1 (ON) or 0 (OFF)
55/267