Selection of operating mode

To facilitate straightforward adaptation of the LMV37.4 to different types of burners, the
LMV37.4 offers automatic configuration of the operating mode. This means that –
derived from parameter 201 – the most important settings relating to the operating mode
are made automatically. Very often in that case, the only manual settings to be made
are those for the fuel-air ratio control system. After selection of the operating mode,
parameters that are not required will be hidden (e.g. oil parameters when firing on gas).
No.
Parameter
Burner operating mode (fuel train, modulating / multistage, actuators, etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
3 = Gp2 mod
4 = Lo mod
5 = Lo 2-stage
6 = Lo 3-stage
7 = G mod pneu
8 = Gp1 mod pneu
9 = Gp2 mod pneu
10 = LoGp mod
11 = LoGp 2-stage
12 = Lo mod 2 fuel valves
13 = LoGp mod 2 fuel valves
201
14 = G mod pneu without actuator
15 = Gp1 mod pneu without actuator
16 = Gp2 mod pneu without actuator
17 = Lo 2-stage without actuator
18 = Lo 3-stage without actuator
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod separate circulation control
24 = Ho 2-stage separate circulation control
25 = Ho mod without circulation control
26 = Ho 2-stage without circulation control
27 = Ho 3-stage without circulation control
28 = G mod mech air actuator only
29 = Gp2 mod mech air actuator only
Basic documentation LMV37.4...
8 Selection of operating mode
91/267
CC1P7546en
17.12.2018