Siemens LMV37.4 Series Basic Documentation page 234

Basic unit with integrated fuel-air ratio control for forced draft burner
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Par.
Parameter
no.
1 = speed standardization active
642
Standardized speed
Index 0 = speed 1
Index 1 = speed 2 (internal monitoring)
Fuel 1:
Index 2 = speed 3
Index 3 = speed 4 (internal monitoring)
643
Setting the speed signal
0 = asymmetrical
1 = symmetrical
644
Setting pulses per revolution
645
Configuration of analog output
0 = DC 0...10 V
1 = DC 2...10 V
2 = DC 0/2...10 V
647
No-load time for speed measurement in modulating
operation [25 ms]
652
VSD behavior when safety loop / burner flange is
open
0 = no VSD control when safety loop / burner flange
is open
1 = VSD control independent of safety loop / burner
flange
653
VSD standstill supervision in standby mode
0 = deactivate
1 = active
661
Internal speed control of LMV37.4  
0 = deactivated (controlled PWM fan)  
1 = activated (VSD)
662
Speed supervision neutral zone
663
Speed supervision low deviation zone
664
Speed supervision: Maximum time outside low
deviation zone
665
Speed supervision: Maximum time outside medium
deviation zone
667
Minimum prepurge speed
234/267
Building Technologies
Number of
Type
Edit
elements
4
Std_u16
read only
1
Selection
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Std_u8
edit
1
Time
edit
1
Time
edit
1
Std_s16
edit / clear
Basic documentation LMV37.4...
28 Parameter list LMV37.4
Value range
Increment
Min.
Max.
650
14000
1
0
1
1
1
6
1
0
2
1
4
8
1
0
1
1
0
1
1
0
1
1
0,5%
3,5%
0,1%
2%
5,5%
0,1%
8 s
16 s
0,2 s
3 s
7 s
0,2 s
40%
100%
0,1%
Default
Password level
setting
write
read
Undefined
---
HF
0
OEM
HF
3
OEM
HF
0
HF
8
OEM
HF
1
HF
HF
1
HF
HF
1
OEM
HF
0,5%
OEM
HF
2%
OEM
HF
8 s
OEM
HF
3 s
OEM
HF
undefined
OEM
HF
CC1P7546en