Error
Diagnostic code
code
20
#
0
1
21
#
0
1
64
22 OFF S
#
0
1
3
5
17
19
21
23
65
67
69
71
81
83
85
87
23
#
240/267
Building Technologies
Meaning for the LMV37.4
Pressure switch-min
No minimum gas / oil pressure
Gas shortage / prevention of startup
Pressure switch-max / POC
Pressure switch-max: Max. gas / oil pressure exceeded
POC: POC open (software version
V02.00)
POC closed (software version
V02.00)
POC open –prevention of startup (software version
Safety loop / burner flange
Safety loop / burner flange open
Safety loop / burner flange open / prevention of startup
Safety loop/burner flange, extraneous light – start prevention
Safety loop/burner flange, air pressure – start prevention
Safety loop/burner flange, combustion pressure – start
prevention
Safety loop/burner flange, extraneous light, combustion
pressure – start prevention
Safety loop/burner flange, air pressure, combustion pressure –
start prevention
Safety loop/burner flange, extraneous light, air pressure,
combustion pressure – start prevention
Safety loop/burner flange, POC – start prevention
Safety loop/burner flange, extraneous light, POC – start
prevention
Safety loop/burner flange, air pressure, POC – start prevention
Safety loop/burner flange, extraneous light, air pressure, POC
– start prevention
Safety loop/burner flange, combustion pressure, POC – start
prevention
Safety loop/burner flange, extraneous light, combustion
pressure, POC – start prevention
Safety loop/burner flange, air pressure, combustion pressure,
POC – start prevention
Safety loop/burner flange, extraneous light, air pressure,
combustion pressure, POC – start prevention
Gas pressure switch-min / heavy oil direct start
Basic documentation LMV37.4...
29 Error code list (all LMV2 types / LMV3 types)
Recommended measures or causes
Check wiring for line interruption
Check wiring for line interruption
Check wiring to see if there is a line interruption.
POC: Check to see if the valve's closing contact is closed
Check wiring.  
Check if the valve closure contact opens when valve is controlled.
Check wiring.  
V02.00)
Check if the valve closure contact opens when valve is controlled.
CC1P7546en