25.5
Manual adjustment (depending on program
module)
25.5.1
Position of actuator or speed of PWM fan in
modulating operation with analog signal
in operating mode or standby,
program sequence for modulating operation via analog preset output and with connected
actuator with potentiometer for position feedback to the LME7...
Basic Documentation LME7...
25 Operation via internal LED
A
Press
for the relative current position of the actuator or
the relative current speed of the PWM fan.
Signal lamp blinks green.
Display shows .oP.
A
Press
(1...3 seconds) for display of the relative current
position or the current speed.
Signal lamp blinks green.
The relative value .57 of the current position is displayed.
Position of actuator 0°
0  value of potentiometer =
0% display
Position of actuator high-fire
>0°
<90° = value of
potentiometer >0  <1000 
= 100% display
Example: Value .57
A
When pressing
(>3 seconds), the point after the
number begins to blink.
When the button is released, the value is displayed for 2
minutes.
Signal lamp blinks green.
Then, the normal display appears.
Display: Value 57, point . blinks.
Actual speed
0 rpm = 0% display
Current speed corresponds
to the rated load speed =
100% display
210/245
CC1P7105en
29.11.2011