Chapter 4
Install the Module

Precautions

52
Follow these precautions for use.

European Hazardous Location Approval

This equipment is intended for use in potentially explosive atmospheres as
defined by European Union Directive 94/9/EC and has been found to comply
with the Essential Health and Safety Requirements relating to the design and
construction of Category 3 equipment intended for use in Zone 2 potentially
explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements is assured by
compliance with EN 60079-15 and EN 60079-0.
WARNING:
• This equipment must be used within its specified ratings as defined by
Rockwell Automation.
• This equipment must be mounted in an ATEX-certified enclosure with a
minimum ingress protection rating of at least IP54 ( as defined in IEC 60529)
and used in an environment of not more than Pollution Degree 2 (as defined in
IEC 60664-1) when applied in Zone 2 environments. The enclosure must have a
tool-removable cover or door.
• Provision shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 140% of the rated voltage when applied in
Zone 2 environments.
• This device must be used only with ATEX-certified Rockwell Automation
terminal bases.
• Do not disconnect equipment unless power has been removed or the area is
known to be nonhazardous.
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014