POINT I/O 2 Current and 2 Voltage Input Analog Modules Installation Instructions
UK and European Hazardous Location Approval
The following applies to products marked
• Are intended for use in potentially explosive atmospheres as defined by UKEX regulation 2016 No. 1107 and European Union Directive 2014/34/EU and has been found to
comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment that is intended for use in Zone 2 potentially
explosive atmospheres, given in Schedule 1 of UKEX and Annex II of this Directive.
• Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN IEC 60079-7 and EN IEC 60079-0.
• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment
given in Schedule 1 of UKEX and Annex II of EU Directive 2014/34/EU. See the UKEx and EU Declaration of Conformity at
• The type of protection is Ex ec IIC T4 Gc according to EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, and
CENELEC ENIEC 60079-7:2015+A1:2018, Explosive atmospheres. Equipment protection by increased safety "e".
• Comply with Standard EN IEC 60079-0:2018, EXPLOSIVE ATMOSPHERES - PART 0: EQUIPMENT - GENERAL REQUIREMENTS, Issue Date 07/2018, CENELEC EN IEC 60079-
7:2015+A1:2018 Explosive atmospheres. Equipment protection by increased safety "e", reference certificate number DEMKO 04 ATEX 0330347X and UL22UKEX2478X.
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification according to UKEX regulation 2016 No. 1107 and ATEX directive 2014/34/EU.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.
IEC Hazardous Location Approval
The following applies to products marked with IECEx certification:
• Are intended for use in areas in which explosive atmospheres caused by gases, vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short
periods. Such locations correspond to Zone 2 classification to IEC 60079-0.
• The type of protection is Ex eC IIC T4 Gc according to IEC 60079-0 and IEC 60079-7.
• Comply with Standards IEC 60079-0, Explosive atmospheres - Part 0: Equipment - General requirements, Edition 7, Revision Date 2017 and IEC 60079-7, 5.1 Edition revision
date 2017, Explosive atmospheres - Part 7: Equipment protection by increased safety "e", reference IECEx certificate number IECEx UL 20.0072X.
• May have catalog numbers followed by a "K" to indicate a conformal coating option.
WARNING: Special Conditions for Safe Use
• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment shall be mounted in an UKEX/ATEX/IECEx Zone 2 certified enclosure with a minimum ingress protection rating of at least IP54 (in accordance
with EN/IEC 60079-0) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in Zone 2 environments.
The enclosure must be accessible only by the use of a tool.
• This equipment shall be used within its specified ratings that are defined by Rockwell Automation.
• Transient protection shall be provided that is set at a level not exceeding 140% of the peak rated voltage at the supply terminals to the equipment.
• The instructions in the user manual shall be observed.
• This equipment must be used only with UKEX/ATEX/IECEx certified Rockwell Automation backplanes.
• Earthing is accomplished through mounting of modules on rail.
• Devices shall be used in an environment of not more than Pollution Degree 2.
• The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
ATTENTION:
• If this equipment is used in a manner that is not specified by the manufacturer, the protection that is provided by the equipment may be impaired.
• Read this document and the documents that are listed in the Additional Resources section about installation, configuration, and operation of this equipment
before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in
addition to requirements of all applicable codes, laws, and standards.
• Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in
accordance with applicable code of practice. In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the
manufacturer for repair. Do not dismantle the module.
• This equipment is certified for use only within the surrounding air temperature range of -20...+55 °C (-4...+131 °F). The equipment must not be used outside
of this range.
• Use only a soft dry anti-static cloth to wipe down equipment. Do not use any cleaning agents.

Before You Begin

This Series C of the POINT I/O™ 2 current and 2 voltage input analog modules can be used with the following:
DeviceNet® and PROFIBUS adapters
ControlNet® and EtherNet/IP™ adapters, using Studio 5000 Logix Designer® application version 20 or later
See the figures to familiarize yourself with major parts of the module, noting that the wiring base assembly is one of the following:
1734-TB or 1734-TBS POINT I/O two-piece terminal base, which includes the 1734-RTB or 1734-RTBS removable terminal block, and 1734-MB mounting base
1734-TOP or 1734-TOPS POINT I/O one-piece terminal base
4
II 3 G:
Rockwell Automation Publication 1734-IN027E-EN-E - June 2023
rok.auto/certifications
for details.