23.1.2.3. List of phase displays

Phase
Function
Ph00
Lockout phase
Ph01
Safety phase
Ph10
Home run
Ph12
Standby (stationary)
Ph22
Fan ramp up time (fan motor = ON, safety valve = ON)
Ph24
Traveling to the prepurge position
Ph30
Prepurge time
Ph36
Traveling to the ignition position
Ph38
Preignition time
Valve proving filling time
Ph39
(test of pressure switch-min when fitted between fuel valves V1 and V2)
Ph40
1st safety time (ignition transformer ON)
Ph42
1st safety time (ignition transformer OFF)
Ph44
Interval 1
Ph50
2nd safety time
Ph52
Interval 2
Ph60
Operation 1 (stationary)
Ph62
Max. time low-fire (operation 2, preparing for shutdown, traveling to low-fire)
Ph64
Switching back to pilot: Modulation to ignition load
Ph65
Switching back to pilot: Interval 2 waiting time
Ph66
Switching back to pilot: Reactivation of ignition + pilot
Ph67
Switching back to pilot: Shutdown of main valves
Ph68
Switching back to pilot: Pilot mode waiting phase
Ph69
Switching back to pilot: Pilot mode waiting phase for burner startup
Ph70
Afterburn time
Ph72
Traveling to the postpurge position
Postpurge time (no extraneous light test)
Ph74
Postpurge time (t3) (abortion when load controller ON)
Ph78
Ph80
Valve proving test evacuation time
Ph81
Valve proving test time atmospheric pressure, atmospheric test
Ph82
Valve proving filling test, filling
Ph83
Valve proving time gas pressure, pressure test
Ph90
Gas shortage waiting time