Siemens LMV37.4 Series Basic Documentation page 220

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Error
Diagnostic code
code
1
2
81
1
82
#
1
2
3
4
5
6
220/235
Building Technologies Division
Industry Sector
Meaning for the LMV37.4... system
Control range limitation at the bottom
Control range limitation at the top
Interrupt limitation speed input
Error during VSD's speed standardization
Timeout of standardization (VSD ramp down time too
long)
Storage of standardized speed not successful
Line interruption speed sensor
Speed variation / VSD ramp up time too long / speed
below minimum limit for standardization
Wrong direction of rotation
Unplausible speed sensor signals
Basic documentation LMV37.4...
29 Error code list
Remedy
523) or the setting for the modulating operating ramp is incorrect (parameter 544)
3. Characteristic of the VSD is not linear. Configuration of the voltage input at the VSD must
accord with that of the basic unit (parameter 645).
4. VSD does not follow quickly enough the changes of the basic unit. Check settings of the VSD
(input filter, slippage compensation, hiding different speeds)
VSD speed was too high
VSD speed was too low
Too much electromagnetic interference on the sensor line
 improve EMC
Timeout at the end of standardization during ramp down of the VSD
 ramp time settings of the VSD are not shorter than those of the basic unit (parameter: 523)
Error during storage of the standardized speed
 lock the basic unit, then reset it and repeat the standardization
Basic unit receives no pulses from the speed sensor:
1. Motor does not turn.
2. Speed sensor is not connected.
3. Speed sensor is not activated by the sensor disk (check distance)
Motor has not reached a stable speed after ramp up.
1. Ramp time settings of the VSD are not shorter than those of the basic unit (parameters 522,
523).
2. Characteristic of the VSD is not linear. Configuration of the voltage input at the VSD must
accord with that of the basic unit (parameter 645).
3. VSD does not follow quickly enough the changes of the basic unit. Check settings of the VSD
(input filter, slippage compensation, hiding different speeds)
4. Speed of VSD lies below the minimum for standardization (650 1/min)
Motor's direction of rotation is wrong.
1. Motor turns indeed in the wrong direction
 change parameterization of the direction of rotation or interchange 2 live conductors.
2. Sensor disk is fitted the wrong way
 turn the sensor disk.
The required pulse pattern (60°, 120°, 180°) has not been correctly identified.
1. Speed sensor does not detect all tappets of the sensor disk
 check distance
2. As the motor turns, other metal parts are detected also, in addition to the tappets  improve
mounting.
3. Electromagnetic interference on the sensor lines
 check cable routing, improve EMC
CC1P7546en