Multistage operation X5-03 (stage 2, pin 3 / stage 3, pin 2)
In multistage operation, 1 or 2 thermostats can be connected to activate the different
burner stages. Multistage operation is possible only when firing on oil.
If neither input «Stage 2» nor input «Stage 3» is active, the burner switches to
«Stage 1».
If input «Stage 2» becomes active, the burner switches to the second stage.
If input «Stage 3» becomes active, the burner switches to the third stage. In that case,
input «Stage 2» can be active or inactive. The third stage can only be activated with 3-
stage operation.
Load controller (LR) (OPEN)
Load controller (LR) (CLOSED)
Load controller (LR) (ON/OFF)
Figure 61: 2-stage operation X5-03
Load controller (LR) (OPEN)
Load controller (LR) (CLOSED)
Load controller (LR) (ON/OFF)
Figure 62: 3-stage operation X5-03
Basic documentation LMV37.4...
9 Connection to load controllers
LMV...
L
Bild 317e/0913
LMV...
L
Bild 318e/0913
ON/OFF
ON/OFF
93/235
CC1P7546en
20.09.2013