Siemens LMV37.4 Series Basic Documentation page 59

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Building Technologies Division
Industry Sector
Functions with adjustable repetition counter
No.
Parameter
194
Repetition limit no flame at the end of safety time (TSA)
1 = no repetition
2...4 = 1...3 repetitions
Recharging time:
Entering into operation
195
Repetition limit heavy oil direct start
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
End of Shutdown phase
196
Repetition limit air pressure failure
1 = no repetition
2 = 1 repetition
Recharging time:
End of Shutdown phase / 24 hours continuous operation
Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
215
16 = constant repetition
Recharging time:
Every 24 hours
Repetition limit pressure switch-min gas
1 = no repetition
2...15 = 1...14 number of repetitions
223
16 = constant repetition
Recharging time:
After the Operation phase
Repetition limit loss of flame
1 = no repetition
2 = 1 repetition
240
Recharging time:
280
After the Operation phase
Parameter assignment:
240 Gas / fuel 0
280 Oil / fuel 0
Basic documentation LMV37.4...
7 Basic unit
59/235
CC1P7546en
20.09.2013