Operation; Normal Display; Display In Standby Mode; Display During Startup/Shutdown - Siemens LME39 Series Basic Documentation

Gas burner controls
Hide thumbs Also See for LME39 Series:
Table of Contents

Advertisement

P
P
Phase
Function
Ph1
Undervoltage
Fault without lockout
Ph2
Extraneous light on burner startup
Ph4
Ph10
Home run
OFF
Standby
Ph21
Air pressure switch check, CPI check
Ph22
Fan ramp up time (fan motor = ON, safety valve = ON)
specified time air pressure signal
Ph24
Actuator traveling to the prepurge position
Ph30
Prepurge time
Actuator traveling to the ignition position
Ph36
Ph38
Preignition time
Ph40
1st safety time (ignition transformer ON)
Ph42
1st safety time (ignition transformer OFF), flame detection time
Ph50
2nd safety time
Ph74
Postpurge time
oP: P1
Operation stage 1 (fuel valve 1 ON)
oP: P2
Operation stage 2 (fuel valve 1/fuel valve 2 ON)
Building Technologies Division
15

Operation

15.1

Normal display

Normal display is the standard display in normal operation, representing the highest
menu level. From the normal display, you can change to the info, service or parameter
level.
15.1.1

Display in standby mode

V
h min s
%
15.1.2

Display during startup/shutdown

15.1.2.1.

Display of program phases

m
3
m
3
/h l
l/h %
15.1.2.2.

List of phase displays

Table 10: List of phase
Basic Documentation LME39...
15 Operation
Unit is in standby mode.
The unit is in Phase 30. The controller calls for heat. The
bar below the
symbol appears. The individual program
phases and controlled components are displayed in
accordance with the program sequence.
43/73
CC1P7106en
08.12.2017