Siemens LMV37.4 Series Basic Documentation page 215

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Par.
Parameter
no.
948
Contact feedback network counter register
950
Required relay state (bit-coded)
Bit 0 = 1: Alarm
Bit 1 = 2: Safety valve
Bit 2 = 4: Ignition
Bit 3 = 8: Fuel valve 1
Bit 4 = 16: Fuel valve 2
Bit 5 = 32: Fuel valve 3 / pilot valve
951
Mains voltage (normalized)
AC 230 V: Voltage = value x 1.683
AC 120 V: Voltage = value x 0.843
954
Intensity of flame
960
Actual flow rate (m³/h, l/h, ft³/h, gal/h)
961
Phase (state for external modules and display)
981
Error memory: Code
982
Error memory: Diagnostic code
992
Error flags
Legend
Std_u8
8 bit integer, not signed
Std_u16
16 bit integer, not signed
Std_u32
32 bit integer, not signed
Std_s8
8 bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1 !
Std_s16
16 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1 !
Std_s32
32 Bit integer, signed
Note
This data type is also used to mark an invalid or non-signed value by using the value of -1 !
Building Technologies Division
Industry Sector
Number of
Type
Edit
elements
14
Std_u8
read only
1
Std_u8
read only
1
Std_u8
read only
1
Std_u8
read only
1
Std_u16
read only
1
Std_u8
read only
1
Std_u8
read only
1
Std_u8
read only
10
Hex_32
reset
Basic documentation LMV37.4...
28 Parameter list LMV37.4...
Value range
Resolution
Min
Max
0
255
1
0
255
1
0 V
255 V
1 V
0%
100%
1%
0
6553.5
0.1
0
255
1
0
255
1
0
255
1
0
0xFFFFFFFF
1
Default
Password level
setting
0
SO
0
Info / Service
0 V
SO
0%
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0
SO
215/235