10.3.6 Setting the minimum and maximum output

When changing the setting of minimum and maximum output after making the
curve settings, following is to be observed:
After leaving the curve settings with completely defined curvepoints, proceed in
modulating operation by setting the minimum / maximum output (parameter 546).
In the case of warm settings, the parameterized output remains active until the minimum
/ maximum output setting is completed. Any change of the minimum / maximum output
is adopted by the parameterized output. Automatic operation becomes active only after
leaving the minimum / maximum output.
This procedure ensures that the system maintains the output set by the user, thus
facilitating troublefree setting of the minimum / maximum output.
Benefits:
- The current output always corresponds to the minimum / maximum output
presently parameterized, or to the system output of the curve settings made last,
which means that the output can be ascertained accurately and free from
interference
- The load sources of low priority (contacts, analog input, building automation output,
manual output) are deactivated
- During the curve and the subsequent minimum/maximum output settings, the
Manual OFF function is deactivated
- Unambiguous and easy-to-understand behavior of the system
Note
If there is no need to limit the output, it is not necessary to set the minimum / maximum
output. In that case, the undefined minimum / maximum output corresponds to a
minimum output of 20% and a maximum output of 100%.
Basic documentation LMV37.4...