7.2.1 Loss of flame
In the event of loss of flame, the unit initiates safety shutdown, followed by a restart, if
required. A repetition counter can be used to select the number of flame losses after
which the unit shall initiate lockout (refer to chapter Repetition counter).
Error
Diagnostic
code
code
7
0
No.
Parameter
Software drop out delay time of flame signal (100 ms)
186
Index 0 = QRB... / QRC... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
194
Repetition limit no flame at the end of safety time (TSA)
1 = no repetition
2...4 = 1...3 repetitions
Recharging time:
Entering into operation
Repetition limit loss of flame
240
1 = no repetition
2 = 1 repetition
Repetition limit loss of flame
280
1 = no repetition
2 = 1 repetition
Caution!
The response time of the flame detector leads to an extension of the second
safety time 2 (TSA2)! This must be taken into consideration when designing the
burner!