Loss Of Flame - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

36/235
Building Technologies Division
Industry Sector

7.2.1 Loss of flame

In the event of loss of flame, the unit initiates safety shutdown, followed by a restart, if
required. A repetition counter can be used to select the number of flame losses after
which the unit shall initiate lockout (refer to chapter Repetition counter).
Error
Diagnostic
code
code
7
0
No.
Parameter
Software drop out delay time of flame signal (100 ms)
186
Index 0 = QRB... / QRC... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
194
Repetition limit no flame at the end of safety time (TSA)
1 = no repetition
2...4 = 1...3 repetitions
Recharging time:
Entering into operation
Repetition limit loss of flame
240
1 = no repetition
2 = 1 repetition
Repetition limit loss of flame
280
1 = no repetition
2 = 1 repetition
Caution!
The response time of the flame detector leads to an extension of the second
safety time 2 (TSA2)! This must be taken into consideration when designing the
burner!
Basic documentation LMV37.4...
7 Basic unit
Meaning for the LMV37.4... system
Loss of flame
CC1P7546en
20.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents