Siemens LMV37.4 Series Basic Documentation page 42

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

42/235
Building Technologies Division
Industry Sector
Heavy oil direct start
When firing on heavy oil, input X9-04 is used for the heavy oil direct start signal.
Parameter 286 can be used to define the time of the evaluation; parameter 287 to define
the maximum waiting time for heavy oil circulation.
No.
Parameter
286
Oil: Evaluation of heavy oil direct start
0 = only start signal in phase 38
1 = evaluation in phase 38...62
287
Oil: Maximum time heavy oil start signal
Error
Diagnostic
Meaning for the LMV37.4... system
code
code
23
2
Heavy oil direct start
For the input, a repetition counter can be parameterized. Here, it is possible to set the
number of errors that are permitted until lockout occurs (refer to subsection Repetition
counter).
No.
Parameter
195
Repetition limit heavy oil direct start
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Basic documentation LMV37.4...
7 Basic unit
CC1P7546en
20.09.2013