Par.
Parameter
no.
501
No-flame positions fuel actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
502
No-flame positions air actuator
Index 0 = home position
Index 1 = prepurge position
Index 2 = postpurge position
503
No-flame speeds VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
522
Ramp up
523
Ramp down
542
Activation of VSD / PWM fan
0 = inactive
1 = active
544
Ramp modulating
545
Lower output limit
undefined = 20 %
546
Upper output limit
undefined = 100 %
600
Actuators
601
Selection of reference point
Index 0 = fuel
Index 1 = air
0 = close (<0°)
1 = open (>90°)
602
Actuator's direction of rotation
Index 0 = fuel
Index 1 = air
0 = counterclockwise
1 = clockwise (exclusively for SQM3...)
606
Tolerance limit of position monitoring [0.1°]
Index 0 = fuel
212/235
Building Technologies Division
Industry Sector
Number of
Type
Edit
elements
3
Std_s16
edit
3
Std_s16
edit
3
Std_s16
edit
1
Std_u8
edit
1
Std_u8
edit
1
Selection
edit
1
Std_u8
edit
1
Output
edit / clear
1
Output
edit / clear
2
Selection
edit
2
Selection
edit
2
Std_u8
edit
Basic documentation LMV37.4...
28 Parameter list LMV37.4...
Value range
Resolution
Min
Max
0 °
90 °
0.1 °
0 °
90 °
0.1 °
0%
100%
0.1%
5 s
40 s
1 s
5 s
40 s
1 s
0
1
1
32 s
80 s
1 s
20%
100%
0.1%
20%
100%
0.1%
0
1
1
0
1
1
0.5 °
0.1 °
Default
Password level
setting
Index
Value
SO
0
1
2
15°
Index
Value
SO
0
1
90°
2
45°
Index
Value
SO
0
0%
1
100%
2
50%
10 s
SO
10 s
SO
0
SO
32 s
SO
undefined
SO (BA)
undefined
SO (BA)
Index
Value
SO
0
1
Password level
1
0
write: OEM
Index
Value
SO
0
0
Password level
1
0
write: OEM
Index
Value
SO
0
1.7°
Password level
CC1P7546en
20.09.2013