Siemens LMV37.4 Series Basic Documentation page 226

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Error
Diagnostic code
code
120
0
121
#
122
#
123
#
124
#
125
#
126
#
127
#
128
0
129
#
130
#
131
#
132
#
133
#
134
#
135
#
136
#
1
137
#
157 (-99)
239 (-17)
240 (-16)
226/235
Building Technologies Division
Industry Sector
Meaning for the LMV37.4... system
Operation no longer allowed
Interrupt limitation fuel counter input
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM read access
Internal error EEPROM write access
Internal error EEPROM access
Internal error EEPROM access - synchronization during
initialization
Internal error EEPROM access – command
synchronization
Internal error EEPROM access - timeout
Internal error EEPROM access - page on abort
Internal error EEPROM register initialization
Internal error EEPROM access – Request
synchronization
Internal error EEPROM access – Request
synchronization
Internal error EEPROM access – Request
synchronization
Restore
Restore started
for further diagnostic codes for error code 136, refer
to error code 137
Internal error – backup / restore
Restore – ok, but backup < data set of current system
Backup – storage of backup in AZL2... faulty
Restore – no backup in AZL2...
Basic documentation LMV37.4...
29 Error code list
Remedy
Too many disturbance pulses at the fuel meters input
 Improve EMC
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Restore of a backup has been started (no error)
New devices require resetting following restore!
For measures, refer to error code 137
Restore successful, but backup data set is smaller than in the current system
Make reset and repeat backup
No backup in AZL2...
CC1P7546en
20.09.2013