Operation; Normal Display; Display In Standby Mode; Display During Startup/Shutdown - Siemens LMO39 Series Basic Documentation

Burner controls
Table of Contents

Advertisement

P
P
Phase
Function
Ph1
Undervoltage
Ph2
Fault without lockout
Ph4
Extraneous light on burner startup
Ph10
Home run
OFF
Standby
Ph21
Heating up time oil preheater
Ph30
Prepurge time
Ph38
Preignition time
Ph40
Safety time (ignition transformer ON)
Ph42
Safety time (ignition transformer OFF)
Ph74
Postpurge time
oP: P1
Operation stage 1 (fuel valve 1 ON)
oP: P2
Operation stage 2 (fuel valve 1/fuel valve 2 ON)
Building Technologies
14

Operation

14.1

Normal display

Normal display is the standard display in normal operation, representing the highest
menu level. From the normal display, you can change to the info, service or parameter
level.
14.1.1

Display in standby mode

V
h min s
%
14.1.2

Display during startup/shutdown

14.1.2.1.

Display of program phases

m
m
/h l
l/h %
3
3
14.1.2.2.

List of phase displays

Table 9: List of phase
Basic Documentation LMO39...
14 Operation:
:
:
:
Unit is in standby mode.
:
The unit is in Phase 30. The controller calls for heat. The
bar below the
symbol appears. The individual program
phases and controlled components are displayed in
accordance with the program sequence.
:
:
CC1P7154en
15.03.2018
35/61