Siemens LMV37.4 Series Basic Documentation page 228

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Error
Diagnostic code
code
168
#
169
#
170
#
171
#
200 OFF
#
201
#
OFF UPr
Bit 0
Valency 1
Bit 1
Valency 2..3
Bit 2
Valency 4..7
Bit 3
Valency 8..15
Bit 4
Valency 16..31
202
#
203
#
204
Phase number
205
#
206
0
207
#
0
1
208
#
209
#
210
0
240
#
245
#
250
#
228/235
Building Technologies Division
Industry Sector
Meaning for the LMV37.4... system
reset attempt
Internal error management
Internal error management
Internal error management
Internal error management
System error-free
Start prevention
No operating mode selected
No fuel train defined
No curves defined
Standardized speed undefined
Backup / restore was not possible
Internal error operating mode selection
Internal error
Program stop
Internal error
Inadmissible combination of units
(basic unit - AZL2...)
Version compatibility basic unit - AZL2...
Basic unit version too old
AZL2... version too old
Internal error
Internal error
Selected operating mode is not released for the basic
unit
Internal error
Internal error
Internal error
Basic documentation LMV37.4...
29 Error code list
Remedy
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
No error
Start prevention due to unparameterized unit
Go to error history, entry 702, for initial cause of the error with shutdown in connection with the first
curve settings
Redefine the operating mode (parameter 201)
Redefine the operating mode (parameter 201).
Make a reset; if error occurs repeatedly, replace the unit
Program stop is active (no error)
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Select a released operating mode for the basic unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
CC1P7546en
20.09.2013