Continue the same way with P2 through P9!
or
F
A
and
or
as well as
and
F
A
and
or
After setting the high-fire point (P9), either a change to parameter 546 (automatic operation) can be
made (ESC) or all curvepoints can be run through in the reverse order.
If the gas pressure is changed, all curvepoints must be checked and – if required – readjusted.
To the next parameter
ESC
192/235
Building Technologies Division
Industry Sector
P
V
h min s
P
V
h min s
P
V
h min s
Completing
parameterization of the
curve
Basic documentation LMV37.4...
27 Parameter level
High-fire position P9 can only be set when
symbol ▲ or ▼ is no longer highlighted.
If required, readjust the gas pressure.
For fuel, keep
F
well as for VSD
F
Press
or
%
When symbol ▲ or ▼ is no longer highlighted,
the next curvepoint P8 can be selected with
.
ESC
The maximum capacity is displayed.
If the display shows - - - -, the maximum
capacity has not yet been specified.
The system can be run up to 100%.
%
You can press
/reset
enabling you to change the maximum capacity.
The minimum capacity is displayed.
If the display shows - - - -, the minimum
capacity has not yet been entered.
The system can be run down to 20%.
%
You can press
/reset
enabling you to change the minimum capacity.
Back to the previous
parameter
depressed, for air
, as
A
and
A
to adjust the value.
to go to editing mode,
to go to editing mode,
CC1P7546en
20.09.2013