Display
Meaning
Sync X11 (green)
2)
Sync status of PROFINET
interface
LED - OFF
LED - flashing (2
Hz)
LED - ON
1) Minimum flashing duration 3 s
2) If no PROFINET IO with IRT has been configured, then generally no synchronization will be made to the send cycle.
Note
During ramp-up of the SIMOTION C, the LEDs on the housing front are briefly illuminated.
You can carry out a detailed diagnosis with a programming device or PC and the engineering
aystem.
Projects cannot be downloaded in STOPU mode.
10.2

Combinations of LED displays

Combination of LED displays
The following table provides an overview of all permissible and/or required LED display
combinations.
SIMOTION C
Operating Instructions, 11/2022, A5E33441428B
Explanations
This LED indicates the synchronization status of the PROFINET interface
X11.
The PROFINET interface has not synchronized yet to the send cycle of IRT or
PROFINET with IRT has not been configured (e.g. only RT or TCP/IP opera‐
tion). If no PROFINET IO with IRT has been configured, then generally there
is no synchronization of the PROFINET interface. If isochronous data has
been configured for the SIMOTION device, the PROFINET interface generates
a local substitute cycle of the same size as the configured send cycle of IRT,
as long as no synchronization has been performed to the send cycle of IRT:
The task system of SIMOTION has synchronized to the local substitute
cycle of the PROFINET interface.
DP interfaces, if configured as isochronous, are synchronized to the local
substitute cycle of the PROFINET interface.
The PROFINET interface has synchronized to the send cycle of IRT. If isochro‐
nous data has been configured for SIMOTION, then the following applies:
The task system of SIMOTION has synchronized to the send cycle of IRT.
DP interfaces, if configured as isochronous, have not synchronized yet to
the send cycle of IRT.
The PROFINET interface has synchronized to the send cycle of IRT. If isochro‐
nous data has been configured, then the following applies:
The task system of SIMOTION has synchronized to the send cycle of IRT.
DP interfaces, if configured as isochronous, are synchronized to the send
cycle of IRT.
If no isochronous data has been configured for SIMOTION, this state indi‐
cates that only the PROFINET interface has synchronized to the send cycle of
IRT. The PROFINET interface is then used to forward the data.
Isochronous data means that data is exchanged with a further device on
PROFINET with configured RT class IRT and isochronous application/device.
Alarm, error, and system messages
10.2 Combinations of LED displays
159