Extraneous Light; No Flame At The End Of Safety Time 1 (Tsa1); Flame Intensity; Supervision Of Flame Detector - Siemens LMV37.4 Series Basic Documentation

Basic unit with integrated air-fuel ratio control for forced draft burners
Hide thumbs Also See for LMV37.4 Series:
Table of Contents

Advertisement

Building Technologies Division
Industry Sector

7.2.2 Extraneous light

Extraneous light in standby mode (phase 12) leads to start prevention, followed by a
restart. Extraneous light during the prepurge phase results in immediate lockout. If
extraneous light occurs during the shutdown phase, the system switches to the safety
phase.
One repetition is permitted. This means that if the error occurs again the next time the
system is shut down, the unit will initiate lockout.
Error
Diagnostic
code
code
4
0
1
2

7.2.3 No flame at the end of safety time 1 (TSA1)

If no flame is established by the end of the first safety time, the unit initiates lockout.
Error
Diagnostic
code
code
2
1
2

7.2.4 Flame intensity

The flame's intensity can be displayed.
It is standardized from 0 to 100%.
No.
Parameter
954
Intensity of flame
Note
Also refer to chapter Intensity of flame during curve settings.

7.2.5 Supervision of flame detector

Error
Diagnostic
code
code
93
3
At the QRB... / QRC... flame detector's input, the LMV37.4... checks the detector for
short-circuits in operation.
Basic documentation LMV37.4...
7 Basic unit
Meaning for the LMV37.4... system
Extraneous light during startup
Extraneous light during shutdown
Extraneous light during startup – start prevention
Meaning for the LMV37.4... system
No flame at the end of safety time 1 (TSA1)
No flame at the end of safety time 2 (TSA2)
Meaning for the LMV37.4... system
Short-circuit of flame detector
37/235
CC1P7546en
20.09.2013

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents