Emergency Mode; Troubleshooting - ProMinent DULCO flex Control Original Operating Instructions

Peristaltic metering pump
Table of Contents

Advertisement

1.4 Emergency mode

1.5 Troubleshooting

Tab. 1: Flash codes of CANopen status LED, top
Colour
Flash code
Green
Lit
Green
Flashing *
Green
Single flashing **
Green
Off
Green
Flickering
Supplementary operating instructions for CANopen
You can guard against the possibility of the CANopen bus control
failing as follows:
1.
Program an auxiliary frequency into the pump that fits best
with your process in emergency mode.
2.
As soon as emergency mode is required, run the pump using
the "external control" terminal on the auxiliary frequency -
see "Peristaltic metering pump DULCO flex Control,
DFXa" - "Installation, electrical".
Doing this will require an external cable and equip‐
ment to issue the auxiliary signal.
If you are in any doubt, seek the advice of our
technical support team.
The CANopen status LED indicates the status of the CAN connec‐
tion.
Operating and fault statuses are displayed by the 3 other LEDs -
see "Operating instructions for peristaltic metering pump DULCO
flex control DFXa".
Cause
Bus status
OPERATIONAL
Bus status
PRE-OPERATIONAL
Bus status
STARTUP
Error (BUSOFF, Error,...)
Bus status
INIT
*
**
Ignore the flash codes for approx. 2 minutes after
connecting the metering pump.
Remedy
- (Pump normal mode)
Wait briefly or start pump
via bus
Wait briefly or set pump
for active bus operation -
see "Set-up" chapter
Test CAN bus
Wait briefly
***
A0203
7