3.2.3 Setting the slave address

'Bus address'
3.2.3.1
Using the
Supplementary operating instructions for PROFIBUS
2.
To switch from
'Information' to 'Fieldbus' , turn the
[Clickwheel] and press it.
'Fieldbus' to 'Inactive / Active' , turn the
3.
To switch from
[Clickwheel] and press it.
'Inactive' to 'Active' , turn the [Clickwheel]
4.
To switch from
and press it.
ð The pump saves the
'Settings è PROFIBUS' menu also appears.
The
The pump is in "Stop" mode. To activate it, press the
[Stop/Start] key. Use the BUS to give the Start command.
All external inputs, such as level monitoring, metering monitoring
and external control (pause, contact input, analogue input), will
function even while the PROFIBUS
reactions you would expect if the pump had no PROFIBUS
tionality - see pump operating instructions. The pump transmits
corresponding information via the PROFIBUS
PC etc.).
The DULCO flex Control DFXa, DFXa is factory-set to
metering.
Even if the fieldbus is set to inactive, the master has read-only
access to the pump data defined in its GSD file.
If the PROFIBUS
is set to
®
ously selected operating mode are reloaded.
If the pump is switched to another operating mode, it stops and can
only be restarted using the
If a master in the PROFIBUS
the slave addresses, manual setting of the slave
address does not apply.
The address is pre-set to "120" for the DULCO flex
Control DFXa, DFXa.
1.
'Menu' : press the
To access the
ð The cursor immediately goes to
'Settings' to 'Fieldbus' , turn the [Clickwheel]
2.
To switch from
and press it.
ð The cursor immediately goes to
'Operating mode' to 'PROFIBUS' turn the
3.
To switch from
[Clickwheel] and press it.
ð The
'Bus address' menu appears.
'Active' setting.
'Active' . They produce the
®
is
to the master (PLC,
®
'Inactive' , the settings for the previ‐
[Stop/Start] key.
segment assigns
®
[Menu] key
'Information' .
'Operating mode' .
®
func‐
®
'Automatic'
47