Debug Data" Register - ProMinent DULCO flex Control Original Operating Instructions

Peristaltic metering pump
Table of Contents

Advertisement

Supplementary operating instructions for Modbus RTU
Register Designation
2200
"Input level warning" level
monitoring
2201
"Input level fault" level moni‐
toring
2202
"Switchover" level monitoring BOO‐
2203
"Warning threshold cont.
mode" level monitoring
2204
"Error threshold cont. mode"
level monitoring
2205
"Unit liquid level" level moni‐
toring
2206
"Total volume storage tank"
level monitoring
2.10.10

"Debug data" register

44
Type
Display / purpose
BOO‐
Parameter is used with 2-stage level monitoring.
LEAN
Without inversion, warning detection is performed via
HIGH level at level warning input
0 - DO NOT INVERT INPUT LEVEL
1 - INVERT INPUT LEVEL
BOO‐
Parameter is used with 2-stage level monitoring.
LEAN
Without inversion, error detection is performed via a
HIGH level at the level error input
0 - DO NOT INVERT INPUT LEVEL
1 - INVERT INPUT LEVEL
This setting can be used to switch between 2-stage
LEAN
and continuous level monitoring
0 - ACTIVATE 2-STAGE LEVEL MONITORING
1 - ACTIVATE CONTINUOUS LEVEL MONITORING
UINT8
With continuous level monitoring:
Specification of a threshold value (in [%] of the max‐
imum level); if this threshold value is not reached, a
warning is generated by the level monitoring
0 ... 100%
UINT8
With continuous level monitoring:
Specification of a threshold value (in [%] of the max‐
imum liquid level); if this threshold value is not
reached, an error is generated by the level moni‐
toring
0 ... 100%
BOO‐
This setting enables the continuous level measure‐
LEAN
ment unit to be selected
0 - LEVEL DATA IN % (RELATIVE TO THE MAX‐
IMUM)
1 - LEVEL IN LITRES (ABSOLUTE FIGURE)
UINT16
Specifies the capacity of the storage tank containing
the feed chemical
1 ... 65535 l
These register inputs are all only for function code "0x03" (Read
only).