Target Operating Parameter" Register - ProMinent DULCO flex Control Original Operating Instructions

Peristaltic metering pump
Table of Contents

Advertisement

Register Designation
1022
Actual operating mode
1023
Actual sub-operating mode
1024
Actual concentration
1026
Switch-on counter
1028
Total operating time
1030
Total revolutions counter
1032
Deletable revolution counter
1034
Total metering quantity
counter
1036
Deletable metering quantity
counter
1040
Remaining metering quantity
1042
Metering quantity of last
stroke
1046
"Liquid level" monitoring
2.10.6

"Target operating parameter" register

Supplementary operating instructions for Modbus RTU
Type
Display / purpose
Enum
0 - EXTERNAL STOP
1 - MANUAL
2 - CONTACT
3 - BATCH
4 - ANALOGUE
Enum
0 = NO SUB-OPERATING MODE
1 - PRIMING
2 - AUXILIARY OPERATION
3 - BATCH TIME CONTROL
4 - BATCH HYDROGRAPH
5 - BATCH ANALOGUE-CONTROLLED VOLUME
6 - BATCH ANALOGUE-CONTROLLED FRE‐
QUENCY
7 - BLEEDING
8 - CALIBRATION
FLOAT32
0.01 ... 100000 ppm
UINT32
Number of previous "Power-ups"
0 ... 2
32
-1
UINT32
0 ... (2
-1)/3600 h
32
UINT32
0 ... 2
32
-1 strokes
UINT32
"Write access" means "Clear counter"
0 ... 2
32
-1 strokes
FLOAT32
0.0 ... (max. FLOAT32) l
FLOAT32
Write access means "Clear counter"
0.0 ... (max. FLOAT32) l
FLOAT32
0.0 l
FLOAT32
Dependent on
- dosing head fitted
- metering type
- ...
UINT16
0 ... 100 %
These register inputs are all for function code "0x03", "0x06", 0x10
and 0x17 (Read / Write).
39

Advertisement

Table of Contents
loading

This manual is also suitable for: