Advanced Configuration" Register - ProMinent DULCO flex Control Original Operating Instructions

Peristaltic metering pump
Table of Contents

Advertisement

2.10.7

"Advanced configuration" register

Register Designation
1400
Pump start behaviour
1407
Analogue input "operating
mode"
1408
"Current 1st user-defined
point" analogue input
1411
"Capacity 1st user-defined
point" analogue input
1413
"Current 2nd user-defined
point" analogue input
1416
"Capacity 2nd user-defined
point" analogue input
1418
"Fault message current too
high" analogue input
1419
"Fault message current too
low" analogue input
Supplementary operating instructions for Modbus RTU
These register inputs are all for function code "0x03", "0x06", 0x10
and 0x17 (Read / Write).
Type
Display / purpose
Enum
Configuration as to how the pump should behave
after a power-up:
0 - ALWAYS OFF
1 - ALWAYS ON
2 - STATUS IMMEDIATELY BEFORE LAST
SWITCH-OFF
Enum
Setting of analogue operating mode:
0 - 0...20mA
1 - 4...20 mA
2 - 20...0mA
3 - 20...4mA
4 - LINEAR CURVE
5 - LOWER SIDE BAND
6 - UPPER SIDE BAND
FLOAT32
For the analogue operating modes - LINEAR
CURVE - LOWER SIDE BAND - UPPER SIDE
BAND this parameter determines the current value
for the first support point of the "Current <-> stroke
rate/capacity" assignment lines
0.0 ... 20.0 mA
FLOAT32
For the analogue operating modes - LINEAR
CURVE - LOWER SIDE BAND - UPPER SIDE
BAND this parameter determines the metering rate
for the first support point of the "Current <->
capacity" assignment lines. Setting in Auto On oper‐
ating mode only
0 ... [max. capacity] l/h
FLOAT32
For the analogue operating modes - LINEAR
CURVE - LOWER SIDE BAND - UPPER SIDE
BAND this parameter determines the current value
for the second support point of the "Current <->
stroke rate/capacity" assignment lines
0.0 ... 20.0 mA
FLOAT32
For the analogue operating modes - LINEAR
CURVE- LOWER SIDE BAND - UPPER SIDE BAND
this parameter determines the metering rate for the
second support point of the "Current <-> capacity"
assignment lines. Setting in Auto On operating mode
only
0 ... [max. capacity] l/h
BOO‐
0 - DO NOT REPORT FAULT
LEAN
1 - REPORT FAULT
BOO‐
0 - DO NOT REPORT FAULT
LEAN
1 - REPORT FAULT
41