Modbus" Register - ProMinent DULCO flex Control Original Operating Instructions

Peristaltic metering pump
Table of Contents

Advertisement

Register
Parameter
4
Serial number
9
Identity code
25
HMI data version
27
Firmware version control
29
Bootloader version control
31
Firmware version power
33
Bootloader version power
2.10.2

"Modbus" register

Register Designation
50
Modbus module active
51
Baud rate
52
Bus address (Modbus)
53
Parity (parity bit)
54
Stop bits (number of stop
bits)
55
Data length (number of data
bits)
56
Termination (bus termination) UINT8
57
Software version of the
Modbus module
59
Hardware version of the
Modbus module
61
Modbus timeout (cyclic
timeout time)
63
Modbus endianness pattern
Supplementary operating instructions for Modbus RTU
Type
Description
STRING[10]
ASCII coding 10 characters
STRING[32]
ASCII coding 32 characters
UINT32
Format: XX.XX.XX.XX (depending on project)
UINT32
Format: XX.XX.XX.XX (depending on project)
UINT32
Format: XX.XX.XX.XX (depending on project)
UINT32
Format: XX.XX.XX.XX (depending on project)
UINT32
Format: XX.XX.XX.XX (depending on project)
These register inputs are all only for function code "0x03" (Read
only).
Type
Display / purpose
UINT8
0 - NOT ACTIVE
1 - ACTIVE
2 - PASSIVE
UINT8
0 - 9600 bits/sec
1 - 19200 Bits/sec
2 - 38400 Bits/sec
UINT8
1... 247
UINT8
0 - NONE
1 - ODD
2 - EVEN
UINT8
0 - 1 STOP BIT
UINT8
1 - 8 BIT
0 - DISABLE
1 - ENABLE
2 - IGNORED
UINT32
Format: XX.XX.XX.XX
UINT32
Format: XX.XX.XX.XX
UINT16
0 ... 10,000 ms
UINT32
Pattern "0xAABBCCDD" is stored in the pump and
can be read out using this register enabling the
endianness of the Modbus access to be determined
from the master