Grounding a cable
Grounding method
Ground the cable and ground cable to the control panel where the GOT and the PLC are installed.
Ground the braided shield section of the cable to the control panel with the cable clamp (AD75CK).
Braided shield
Cable clamps
For the attachment details of
cable clamps, refer to
AD75CK-type Cable Clamping
Instruction Manual
<IB-68682>.
Precautions
Do not arrange the cable clamp close to the other cables that are not clamped.
The noise from the control panel may enter the cable clamp and adversely affect the GOT.
5 EMC DIRECTIVE
46
5.2 EMC Directive Requirements