Wiring Example; Got's Ground - Mitsubishi Electric GOT SIMPLE Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT SIMPLE Series:
Table of Contents

Advertisement

Tools
Use a small driver with a straight, untapered blade as shown below to tighten the power terminals.
Use a driver
with a flat end
0.6mm
3.5mm
Manufacturer
Phoenix Contact Inc.

Wiring example

Connect the power supply to the power terminals on the back panel of the GOT.
Class D
grounding
+10%
DC24V
- 15%
Tightening torque for the power terminals: 0.5 to 0.6N·m

GOT's ground

Grounding the GOT and other devices
Make sure to carry out the followings for grounding.
• Carry out the independent grounding if possible. Provide class D (class 3) grounding. (Ground resistance must be 100Ω or
less.)
• If the independent grounding is impossible, carry out the shared grounding as shown in fig.2) below.
Other
GOT
device
Grounding
(100Ω or less)
(1) Independent ground
...... Best condition
2
• Use the cable of 2mm
or longer for grounding. Set the grounding point closer to the GOT to make the grounding cable
short as possible.
Model
SZS 0.6
Other
GOT
device
Grounding
(100Ω or less)
(2) Shared grounding
...... Good condition
3.5
Other
GOT
device
(3) Common grounding
...... Not allowed
7.1 Power Supply Wiring
7
7 WIRING
55