Got Ip Address Setting; Standard; Display Operation Of Got Ip Address - Mitsubishi Electric GOT SIMPLE Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT SIMPLE Series:
Table of Contents

Advertisement

11.2

GOT IP Address Setting

This section describes the GOT Ethernet setting.
The GOT Ethernet setting can also be set with drawing software. For details, refer to the following.
GT Designer3 (GOT2000) Screen Design Manual

Standard

The table below shows the communication setting items and setting range.
Communication setting items
IP Address
*1
Subnet Mask
*1
Default gateway
Per. S/W port No.
Transparent port No.
*1 Set the value "0.0.0.0" when not using the subnet mask and default gateway.

Display operation of GOT IP address

Main Menu
11 COMMUNICATION INTERFACE SETTING (COMMUNICATION SETTING)
84
11.2 GOT IP Address Setting
Setting range
0.0.0.1 to 223.255.255.254
192.0.0.0 to 255.255.255.252
0.0.0.1 to 223.255.255.254
1024 to 5010, 5014 to 49152, 49171 to 65534
1024 to 5010, 5014 to 49152, 49171 to 65534
Touch
[Comm. Setting].
Remark
If a value outside the setting range is entered, the error message
"SET NUMBER IS INCORRECT." appears.
Set the port number for the GOT download.
Set the port number for the transparent of the GOT.
Comm. Setting
GOT IP Address
Touch
[GOT IP Address].

Hide quick links: