16 GOT SELF CHECK (DEBUG)
264
16.3 FX3U-ENET-ADP Communication Setting Function
5.
When the screen shown on the left appears, the
changed communication set value of the FX3U-ENET-
ADP is written normally to the CPU. For making valid
the contents of setting, turn OFF the power of the CPU,
and then turn it ON again. Change the setting of the
subnet mask pattern and default router IP address using
the same procedure if necessary. An error message
appears in the following cases. Touch the
return to the step 1., and perform the setting procedure
again.
When the CPU is running
The following error message appears. Stop the running
status of the CPU.
When a communication error occurs
Set the communication between the GOT and the CPU to the
normal status.
When the memory cassette is write-protected
Set to OFF the write-protect switch of the memory cassette.
When writing to the CPU is protected by the keyword
Clear the protection by the keyword against writing.