Power Supply Wiring; Cable Types And Wire End Processing - Mitsubishi Electric GOT SIMPLE Series User Manual

Graphic operation terminal
Hide thumbs Also See for GOT SIMPLE Series:
Table of Contents

Advertisement

7.1

Power Supply Wiring

Connect the power supply to the power terminals on the back panel of the GOT.
Use a specified size power supply wire to prevent voltage drop, and tighten the terminal screws firmly to a specified torque.
Do not exceed the number of wires that are allowed to be connected.
Secure the wires to prevent stress from being directly applied to the terminal block or wire connections.

Cable types and wire end processing

Process the end of the electrical wire (solid or stranded), or attach a ferrules with plastic sleeve to the wire end.
Terminal screws should be tightened to between 0.3 to 0.5N·m. Terminal screws must be secured to prevent a loose
connection thus avoiding a malfunction.
When tightening terminal screws, do not exceed the specified torque. Failure to do so may cause equipment failures or
malfunctions.
Electrical wire size
Electrical wire size
Solid wire
2
0.5 to 2.5mm
AWG20 to AWG14
Wire end processing
■Connecting the wire directly
Twist the end of the stranded wire. Make sure there are no wire whiskers.
Do not solder the wire end.
Approx. 6mm
■Using a ferrules with plastic sleeve to connect the wire
A wire with a too thick of a wire sheath may not fit the insulation sleeve. Refer to the outline drawing for how to select the
proper size wire.
Insulation sleeve
2.8 to 4.2mm
14 to 18mm
Manufacturer
Phoenix Contact Inc.
7 WIRING
54
7.1 Power Supply Wiring
Stranded wire
0.5 to 2.5mm
AWG20 to AWG14
Terminal
contact
section
8 to 12mm
Model
AI 0.75-8BU (0.5 to 0.75mm
AI 1.0-8RD (0.75 to 1.0mm
AI 1.5-8BK (1.0 to 1.5mm
AI 2.5-8BU (1.5 to 2.5mm
2
2
)
2
)
2
)
2
)
Ferrules with plastic sleeve
2
0.5 to 2.5mm
AWG20 to AWG14
Crimper type
CRIMPFOX UD6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs21

Table of Contents