Setting of response performance and load to motor mass ratio by minute position
detection method
When using the minute position detection method, set the response performance with [Pr. PL17.0 Response selection], the
load to motor mass ratio with [Pr. PL17.1 Load to motor mass ratio/load to motor inertia ratio]. If the load to mass of the linear
servo motor primary-side ratio is unknown, perform the magnetic pole detection by the position detection method, and then
perform the auto tuning to set an estimated value.
• [Pr. PL17.0 Response selection]
Setting value
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Initial value: 0
• [Pr. PL17.1 Load to motor mass ratio/load to motor inertia ratio selection]
Setting value
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Initial value: 0
Setting of identification signal amplitude by minute position detection method
If [AL. 032 Overcurrent], [AL. 050 Overload 1], [AL. 051 Overload 2], or [AL. 0E1 Overload warning 1] occurs at the magnetic
pole detection by the minute position detection method, set a smaller value for [Pr. PL18 Magnetic pole detection - Minute
position detection method - Identification signal amplitude]. Basically, [Pr. PL18] does not need to be changed from the initial
value.
10 USING A LINEAR SERVO MOTOR
366
10.3 Startup [A]
Responsiveness
Low response
Middle response
High response
Load to motor mass ratio/load to motor inertia ratio
10 times or less
10 multiplier
20 multiplier
30 multiplier
40 multiplier
50 multiplier
60 multiplier
70 multiplier
80 multiplier
90 multiplier
100 multiplier
110 multiplier
120 multiplier
130 multiplier
140 multiplier
150 times or more

Advertisement

Table of Contents
loading

Table of Contents