Group Sleeping Function - Danfoss VFD500 Series Manual

Table of Contents

Advertisement

VFD500 high performance vector control frequency inverter user manual
Upper Detection
P40.38
PID operation at
P40.39
P40.40
P40.41
PID offset digital
P40.42
Sleep mode and
P41.00
P41.01
time of PID
0.000s~30.000s
feedback loss
0-No PID operation at stop

stop
1-PID operation at stop
PID command
for accel and
0.0s~6000.0s
decel time
0-digital setting

PID offset
1-AI1

selection
2-AI2

3-AI3(option card)
-100.0%~100.0%
setting

41 Group Sleeping function

Unit's digit: sleep mode selection
0:no sleep function
1:sleep by frequency
2:AI1 sleep (AI1 as pressure feedback)

3:AI2 sleep(AI2 as pressure feedback)
4:AI3 sleep (AI3 as pressure feedback)

3:AI4 sleep(AI4 as pressure feedback)
Ten's digit :wake up mode selection
0:wake up by frequency
1:AI1 wake up (AI1 as pressure
feedback)

2:AI2 wake up (AI2 as pressure
feedback)
3:AI3 wake up (AI3 as pressure
feedback)

4:AI4 wake up (AI4 as pressure
feedback)
Hundred's digit:Sleep wake direction
selection
wake up
0: positive direction
selection
Sleep source (AI1 ~ AI4) > P41.03, inverter
will sleep
Wake-up source (AI1 ~ AI4) < P41.04, the
inverter will wake up
1: reverse direction
Sleep source (AI1 ~ AI4) < P41.03, inverter
sleep
Wake-up source (AI1 ~ AI4) > P41.04, the
inverter wakes up.
When the sleep source and wakeup
source are the same, please pay
attention to the size relationship of
P41.03 and P41.04. If the parameter
setting is unreasonable, when the
wake-up condition is selected, even if
the sleep condition is established, the
sleep state cannot be entered, and
special attention is required when
using.
Sleep setting
0.00Hz~600HZ,It will sleep if value is less
value by
than this value
frequency
101
Chapter 5 function code table
0.000s
0
0.0s
0
0.0%
010
0.00Hz